Ill. Admin. Code tit. 35, § 616.624 - Design and Operating Requirements
The owner or operator must:
a) Maintain a written record inventorying all
fertilizers stored or handled at the unit.
b) At least weekly when fertilizers are being
stored, inspect storage containers, tanks, vents, valves, and appurtenances for
leaks or deterioration caused by corrosion or other factors. If a leak or
deterioration is found in any of these devices, the owner or operator must
immediately repair or replace the device. The owner or operator must maintain a
written record of all inspections conducted under this Section and of all
maintenance relating to leaks and deterioration of these devices.
c) Store all containers containing
fertilizers (except anhydrous ammonia) within a fertilizer secondary
containment structure, if the containers are stored outside of a roofed
structure or enclosed warehouse. For this subsection, a fertilizer secondary
containment structure is a structure that complies with the design standards in
8 Ill. Adm. Code 255.
d) Maintain
all written records required under this Section at the site. The owner or
operator must provide the written records to the Agency upon request.
Notes
Board Note: Owners or operators of facilities or units subject to this Part may also be subject to regulations under 8 Ill. Adm. Code 255.