Ill. Admin. Code tit. 41, § 105.10 - Fireworks Plant Fencing
a)
Specifications and Maintenance. The fence required by section 13 (a) of the
fireworks act referred to above, Ill. Rev. Stat., ch. 1271/2, par. 113 (a),
shall substantially meet the specifications set forth in Rules 1.01 through
1.06 (41 Ill. Adm. Code Section 100.82(a) through (g)) and shall be properly
maintained at all times.
b) Height.
The fence shall be not less than seventy-two (72) inches high at all
points.
c) Support. The fence shall
be firmly attached to or rigidly supported by steel or wood posts set on not
more than ten (10) foot centers anchored in firm ground not less than
twenty-four (24) inches deep.
d)
Top Arm. The fence shall have an arm securely fastened on top and extending
outward at an angle of not less than thirty-five (35) degrees nor more than one
hundred eighty (180) degrees, except that the arm on a gate may be vertical.
The arm atop the fence shall be not less than twelve (12) inches wide and
extend the length of the fence. The arm atop the fence shall carry three (3)
strands of barbed wire spaced not less than five (5) inches apart. The barbed
wire shall consist of a double cable of no. 14 gauge, or heavier, galvanized
steel wire with two or more point barbs tightly and doubly twisted around and
through the cable wires and set not more than six (6) inches apart.
e) Fence Structure. The vertical part of said
fence shall consist of line and stay wires. The bottom line wire shall be flush
with the ground. The stay wires shall be welded to or interwoven with the line
wires and spaced on not more than two (2) inch centers forming a rectangle or
diamond shape mesh. The line wires and stay wires may be interwoven as to form
chain links. All line wires and stay wires shall be of no. 11 gauge, or
heavier, steel galvanized wire.
f)
Gates. All openings in the fence shall be equipped with metal gates which shall
be kept securely locked at all times, except when in actual use, provided that
the main gate of the plant may be left open during the regular hours of plant
operation while in plain view of and under observation by authorized employees
or guards.
g) Material. Whenever a
particular material is specified in these rules and regulations, material of at
least equivalent strength and quality may be substituted.