Ill. Admin. Code tit. 41, § 174.440 - Dispensing or Delivery of Flammable or Combustible Motor Fuels from Tank Vehicles
Dispensing or delivery of flammable or combustible motor vehicle fuels from tank vehicles is allowed at sites used for the parking, operation or maintenance of a commercial vehicle fleet under the following conditions:
a) The site is located in
a county with 3,000,000 or more inhabitants or a county contiguous to a county
with 3,000,000 or more inhabitants and:
1) The
site is not normally accessible to the public and has been approved by
OSFM.
2) The vehicles being fueled
are part of a fleet of commercial vehicles that are normally parked, operated
or maintained at the fueling site.
3) An inspection of the fueling site has been
made and approval granted in the form of a permit issued by OSFM. An inspection
of the facility may be made at any time. The permit application may be found at
https://www2.illinois.gov/sites/sfm/About/Divisions/Fire-Prevention-and-Building-Safety/Pages/Mobile-Fueling.aspx.
4) Electrical devices and wiring in areas
where fuel is dispensed are in accordance with the edition of NFPA 70 in effect
at the time the mobile fueling site was constructed.
5) Dispensing locations are at least 50 feet
from structures or combustible storage, including structures or storage on
adjacent properties.
6) Signs are
posted prohibiting smoking or open flames within 25 feet of the fuel tanker and
the point of fueling.
b)
The tank vehicle is owned and operated by a company licensed by OSFM to perform
mobile fueling.
c) The tank vehicle
complies with the requirements of NFPA 385, incorporated by reference in
Section 174.210 and has been approved by
OSFM.
d) The tank vehicle displays
a mobile-fueling sticker issued by OSFM.
e) The dispensing hose does not exceed 50
feet in length.
f) The dispensing
nozzle is a listed automatic-closing type with a latch-open device.
g) Nighttime deliveries are only be made in
adequately lighted areas.
h) The
tank vehicle's flasher lights are in operation while dispensing.
i) Fuel expansion space is left in each fuel
tank to prevent overflow in the event of temperature increase.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.