Unattended self-service motor fuel dispensing facilities and
islands shall comply with all of the requirements for attended motor fuel
dispensing facilities and islands (see Section
175.210) with the additions and
modifications provided in this Section. Requirements specific to control
stations and attendants in Section
175.210 are not applicable to
unattended facilities. If a motor fuel dispensing facility is to be operated as
an unattended station during any portion of a day, it shall meet the standards
for unattended operation.
a) Minimum
Signage. Signs shall be posted in all-weather materials by each actuator (or at
the dispenser if the actuator is an integral part of the dispenser) and the
lettering shall be not less than 7/8 inch high. The top of the signs shall be
mounted no higher than 10 feet above grade, or at a height approved by OSFM,
and shall include the following wording, at a minimum:
1) "No smoking";
2) "Turn off engine";
3) "Containers for gasoline must be
red";
4) "Containers for kerosene
must be blue";
5) "It is dangerous
and unlawful to fill unapproved containers with gasoline, diesel or
kerosene";
6) "In case of fire or
spill use EMERGENCY STOP located at..." (owner must insert the locations of the
emergency stops);
7) "EMERGENCY
STOP activation transmits a fire alarm to the fire department".
b) Easily accessible emergency
stops must be provided at each dispensing island. Each emergency stop shall be
identified by an approved sign on all-weather materials stating "EMERGENCY
STOP" in 2 inch red capital letters. Combinations of dispenser islands where a
master and corresponding satellite dispenser are used to fuel saddle tanks on
trucks and similar vehicles shall be considered as being on one island so long
as the piping and electronics are one integral unit and the satellite unit is
controlled by the master dispensing unit. In addition, there shall be at least
one emergency stop located at least 20 feet but not more than 100 feet from
each dispenser. When more than one emergency stop is provided, all devices
shall be interconnected so that activation of one emergency stop activates all
the emergency stops. Stations with only one island may elect to utilize a
single emergency stop located at least 20 feet but not more than 100 feet from
each dispenser, or at a location approved by OSFM. A sign shall be placed at
each emergency stop stating that activation of the emergency stop "transmits a
fire alarm to the fire department". Resetting from an emergency stop activation
shall require manual intervention by the owner or attendant and shall be
accomplished only after the condition that caused the activation has been
corrected.
c) Fire Alarm Systems
1) Activation of any emergency stop at the
facility shall automatically transmit an alarm to local emergency fire services
providers by sending a signal via one of the following mechanisms, which shall
meet the requirements of NFPA 72:
A) Auxiliary
alarm system;
B) Central station
alarm connection;
C) Proprietary
alarm receiving facility or system;
D) Remote station alarm connection;
or
E) When the mechanisms in
subsections (c)(1)(A) through (c)(1)(D) are not available, an alternate plan
for notification of local emergency services meeting NFPA 70 and NFPA 72 and
approved by OSFM in advance of the use.
2) The fire alarm system shall be installed,
tested and maintained according to NFPA 70 and NFPA 72. The alarm system must
also meet the alarm system requirements of subsections (h)(1)(C) and (h)(2)(D),
including the requirement for an audible alarm when triggered.
d) All emergency stops shall be
tested, and all shear valves visually inspected, at least annually to ensure
that they are functioning properly and that the dispenser is mounted properly.
Documentation of annual emergency stop testing and shear valve inspection shall
be kept at the motor fuel dispensing facility and available for examination by
a representative of OSFM. If documentation of annual testing of emergency stops
is not available, the facility shall be subject to demonstration of this
equipment during inspection by OSFM.
e) Actuators may use currency, coins, keys,
cards or electronic means to activate dispensers and pumps.
f) Dispensing devices or actuators must limit
the delivery of product in a manner that requires reactivation of the latch
open (hold-open) device for any dispensing beyond the following amounts:
1) Motor vehicle fuels (Class I, II and III)
A) Class I liquids (gasoline, gasohol,
ethanol, motor fuel blends) - maximum 100 gallons.
B) Class II and III liquids (diesel fuel) -
maximum 250 gallons.
2)
Kerosene (grade K-1 only) - 18 gallons.
3) Other Class I, II and III liquids - 6
gallons.
g) Except for
farms, when kerosene is to be dispensed at unattended motor fuel dispensing
facilities, only grade K-1 kerosene shall be dispensed.
h) All unattended motor fuel dispensing
facilities shall have installed and maintained equipment and systems that meet
the requirements of subsection (h)(1) or (h)(2), although local governments may
require option (h)(1) or (h)(2):
1) Unattended
dispensing areas for Class I, II and III liquid motor fuels utilizing this
option shall be protected by an automatic fire suppression systems meeting the
standards of UL 1254 and NFPA 17. If a fire suppression system meeting these
requirements is installed, no fire extinguishers are required. In the event of
a fire suppression system discharge, the fuel dispensing facility shall not be
returned to service until the suppression system is recharged and fully
operational in the area protected by the system. The fire suppression system
shall, when activated:
A) Automatically
activate an emergency stop that is equipped so that all fuel dispensing units
and submersible pumps would be stopped by the activation.
B) Sound a local alarm notification device
that is audible throughout the dispensing area and meets the requirements of
NFPA 72.
C) Automatically transmit
an alarm, through a system installed, tested and maintained according to NFPA
70 and 72, to local emergency fire services providers by sending a signal via
one of the following mechanisms, which shall meet the requirements of NFPA 72:
i) Auxiliary alarm system;
ii) Central station alarm
connection;
iii) Proprietary alarm
receiving facility or system;
iv)
Remote station alarm connection; or
v) Where the mechanisms in subsections
(h)(1)(C)(i) through (iv) are not available, an alternate plan for notification
of local emergency services meeting NFPA 70 and NFPA 72 and approved by OSFM in
advance of the use.
D)
Include extinguishing agent discharge nozzles mounted above dispensers and at
or near ground level to discharge agent underneath vehicles being
fueled.
2) Unattended
dispensing areas for Class I, II and III motor vehicle fuels electing this
option shall be equipped with portable fire extinguishers and a fire detection
system located under a weather enclosure canopy (unless written documentation
is submitted verifying that the detection system will operate properly without
a canopy).
A) The system shall detect a fire
in the dispensing area through the use of rate compensation, rate of rise or
flame sensing detectors. The installation must meet the requirements of NFPA
72.
B) Activation of the system
shall automatically activate an emergency stop that is equipped so that all
fuel dispensing units and submersible pumps would be stopped by the
activation.
C) Activation of the
system shall cause the sounding of a local alarm notification device audible
throughout the dispensing area and meeting the requirements of NFPA
72.
D) Activation of the system,
which shall be installed, tested and maintained according to NFPA 70 and 72,
shall automatically transmit an alarm to local emergency fire services
providers by sending a signal via one of the following mechanisms, which shall
meet the requirements of NFPA 72:
i) Auxiliary
alarm system;
ii) Central station
alarm connection;
iii) Proprietary
alarm receiving facility or system;
iv) Remote station alarm connection;
or
v) Where the mechanisms in
subsections (h)(2)(D)(i) through (iv) are not available, an alternate plan for
notification of local emergency services meeting NFPA 70 and NFPA 72 and
approved by OSFM in advance of the use.
E) Fire extinguishers meeting the
requirements of 41 Ill. Adm. Code
174.350 shall be installed and
maintained at each island and at the emergency stop. Cabinets, or other
enclosures for extinguishers, shall not require breaking of glass or other acts
that could injure users attempting to access the extinguishers, though doors,
panels and local alarm systems may be provided for these enclosures at the
owner's option.
3) The
annual system testing required under NFPA 17 and NFPA 72 must be documented and
the documents regarding this testing kept at the facility or available within
30 minutes or before OSFM completes its inspection, whichever is
later.
4) In meeting the
requirements of subsections (c) and (h), facilities in existence as of
September 1, 2010 shall have the option of complying with the editions of NFPA
17, NFPA 70 and NFPA 72 and UL 1254 incorporated by reference in 41 Ill. Adm.
Code
174.210 or the OSFM alarm system
and fire suppression and fire detection system requirements in effect at the
time of their installation.
5) Any
changes to either fire suppression or fire detection systems and related alarms
require that the facility notify OSFM in writing at least 60 days in advance of
the change.
i) At least
once each year the facility shall verify that the alarm notification devices
required under subsections (c) and (h) are working. The facility shall record
the verification date and results on a record kept along with the other
facility records.