Ill. Admin. Code tit. 77, pt. 250, subpt. W, tbl. E - Piping Locations for Oxygen, Vacuum and Medical Compressed Air
|
Location |
Oxygen |
Vacuum |
Compressed Air |
|
Patient Room for Adult Medical/Surgical Care |
A |
A |
|
|
Patient Room for Postpartum Care & Pediatrics |
A |
F |
|
|
Examination and Treatment Rooms for Nursing Unit |
D |
D |
|
|
Patient Room for Intensive Care |
C |
C |
B |
|
Normal Newborn Nursery |
A |
B |
A |
|
Special Care & Observation Nursery |
B |
B |
A |
|
General Operating Room |
E |
E |
E |
|
Cystoscopy and Special Procedure Room |
D |
D |
D |
|
Recovery Room for Surgical and Obstetrical Patients |
B |
B |
A |
|
Delivery Room |
E |
E |
|
|
Labor Room |
A |
A |
|
|
Treatment Room for Emergency Care |
D |
D |
|
|
Autopsy Room |
- |
D |
|
|
Anesthesia Workroom |
- |
D |
|
A |
= |
One outlet accessible to each bed One outlet may serve 2 beds |
|
B |
= |
One outlet for each bed |
|
C |
= |
Two outlets for each bed |
|
D |
= |
One outlet |
|
E |
= |
Two outlets |
|
F |
= |
One outlet provided if required by the narrative |
Notes