Ill. Admin. Code tit. 77, § 250.1940 - Ventilation, Heating, Air Conditioning, and Air Changing Systems
Ventilation, heating, air conditioning, and air changing systems shall be provided, comply with Subpart T or Subpart U, and shall:
a) be maintained in good repair
and shall be operated in a manner which will prevent the spread of infection
and provide for patient comfort;
b)
be maintained and operated in such manner that air shall not be circulated from
operating rooms, patient isolation rooms, laboratories in which work is done in
pathology, virology or bacteriology, autopsy rooms, kitchen and dishwashing
areas, toilet and bathrooms, janitors' closets, storage rooms, shop areas and
soiled linen to any other part of the facility;
c) be provided, as needed, with acceptable
air filtration equipment that is cleaned and serviced at adequate intervals;
and
d) assure that the relative
humidity is maintained at a minimum of 50 percent in those areas where
conductive floors are required.
Notes
Amended at 5 Ill. Reg. 507, effective December 29, 1980
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.