Ill. Admin. Code tit. 77, § 250.2450 - Details
a)
Compartmentation, exits, automatic extinguishing systems, and other details
relating to fire prevention and fire protection shall comply with requirements
listed in the appropriate sections of NFPA 101, Life Safety Code.
b) Items such as drinking fountains,
telephone booths, vending machines, and portable equipment shall be located so
as not to restrict corridor traffic or reduce the corridor width below the
required minimum.
c) Doors
1) Doors to patient rooms shall not be
lockable from inside the room. Hospitals shall have policies and procedures for
readily gaining access to a locked bathroom in a patient's room. (Section 11.6
of the Act)
2) Special Locking
Arrangements: Electronic locking devices may be installed at specific locations
to restrict egress or ingress for patient/staff safety or security, provided
that each of the following is complied with and after receiving approval from
the Department:
A) The facility shall submit
a narrative to the Department providing a rationale for having a locked door in
a required means of egress. The rationale shall relate to security
issues.
B) The building shall be
protected by a sprinkler or fire detection system approved by the
Department.
C) All locking system
components shall be U.L. listed.
D)
Cross corridor, smoke, or control doors that are located in a required means of
egress may be secured only with electronic locks and automatic release devices.
The use of only manual keys or tools to unlock the door is not
permitted.
E) Locked doors shall
have continuous staff supervision (direct or electronic remote).
F) No other type of locking arrangement may
be used in a required means of egress.
G) All locked doors shall release
automatically with actuation of the fire alarm system.
H) All doors shall release automatically with
loss of electrical power to the locking device.
I) All delayed egress locks shall initiate an
irreversible process that will release the lock within 15 seconds whenever a
force of not more than 15 pounds is continuously applied to the release device
(lever type handle or panic bar) for a period of not more than three seconds.
Relocking of such doors shall be by manual means only. Operation of the release
device activates a sign in the vicinity of the door to assure those attempting
to exit that the system is functional. Delays of up to 30 seconds may be
acceptable based on the program narrative.
J) Permanent signs shall be posted on
electronic locked doors that state the action required to open the door.
Electronic delayed egress type doors shall state: "Push until alarm sounds.
Door will be opened in 15 seconds." Sign letters shall be at least 1 inch high
with 1/8-inch stroke. Signs may be omitted for security reasons based on the
Department's review of the hospital's written rationale.
K) Emergency lighting shall be provided at
all locked door locations.
L) The
local fire department shall be fully apprised of locked doors or units and all
related details of the system.
M)
Any discharge exit door may be locked against entry.
N) Additional electronic release of locked
doors initiated from a 24/7 staff duty station or an ADA compliant release
device located within 5 feet of the door shall be provided. The duty station
shall be located within the locked unit and staff shall be able to observe the
door directly to by remote video.
O) No more than two electronic locking
devices may be installed in any path of travel to exit discharge, one of which
may be delayed egress.
P) Complete
smoke detection shall be provided throughout the entire secured unit.
d) The minimum width of
all doors to rooms needing access for beds or stretchers shall be 3 feet, 8
inches. Doors to rooms needing access for wheelchairs shall have a minimum
width of 2 feet, 10 inches.
e)
Doors on all openings between corridors and rooms or spaces subject to
occupancy, except elevator doors, shall be swing type. Openings to showers,
baths, patient toilets, and other small wet-type areas not subject to fire
hazard are exempt from this requirement. Sliding doors with a break and swing
feature are acceptable.
f) Doors,
except those to spaces such as small closets that are not subject to occupancy,
shall not swing into corridors in a manner that might obstruct traffic flow or
reduce the required corridor width. (Large walk-in type closets are considered
as occupiable spaces.)
g) Windows
shall be designed so that persons cannot accidentally fall out of them when
they are open, or shall be provided with guards.
h) Glazing
1) Doors, sidelights, borrowed lights, and
windows in which the glazing extends down to within 18 inches of the floor
(thereby creating possibility of accidental breakage by pedestrian traffic)
shall be glazed with safety glass or plastic glazing material that will resist
breaking and will not create dangerous cutting edges when broken. Similar
materials shall be used in wall openings or recreation rooms and exercise
rooms. Safety glass or plastic glazing materials shall be used for shower doors
and bath enclosures. Fire-rated glass shall be used where required for fire
safety.
2) Safety glass or plastic
glazing materials as noted above shall be used in windows and doors in patient
areas of psychiatric facilities, if required by the program. See the Safety
Glazing Materials Act for other requirements.
i) Where labeled fire doors are required,
these shall be certified by an independent testing laboratory as meeting the
construction requirements equal to those for fire doors in NFPA 80, Standard
for Fire Doors and Fire Windows. Reference to a labeled door includes labeled
frame and hardware.
j) Elevator
shaft openings shall be Class B 11/2-hour-labeled fire doors.
k) Linen and refuse chutes shall meet or
exceed the following requirements:
1) Service
openings to chutes shall not be located in corridors or passageways but shall
be located in a room of construction having a fire-resistance of not less than
one hour. Doors to such rooms shall be not less than Class C 3/4-hour-labeled
doors.
2) Service openings to
chutes shall have approved self-closing Class B 11/2-hour-labeled fire
doors.
3) The minimum
cross-sectional dimension of gravity chutes shall be not less than 2
feet.
4) Chutes shall discharge
directly into collection rooms separated from incinerator, laundry, or other
services. Separate collection rooms shall be provided for trash and for linen.
The enclosure construction for such rooms shall have a fire-resistance rating
of not less than two hours, and the doors thereto shall be not less than Class
B 11/2-hour-labeled fire doors. External discharge containers need not be
enclosed.
5) Gravity chutes shall
extend through the roof with provisions for continuous ventilation as well as
for fire and smoke ventilation. Openings for fire and smoke ventilation shall
have an effective area of not less than that of the chute cross-section and
shall be not less than 4 feet above the roof and not less than 6 feet clear of
other vertical surfaces. Fire and smoke ventilating openings may be covered
with single strength sheet glass or stronger.
6) See NFPA 82, Standard on Incinerators and
Waste and Linen Handling System and Equipment for other requirements.
l) Dumbwaiters, conveyors, and
material-handling systems shall not open directly into a corridor or exitway
but shall open into a room enclosed by construction having a fire-resistance
rating of not less than one hour and provided with Class C 3/4-hour-labeled
fire doors. Service entrance doors to vertical shafts containing dumbwaiters,
conveyors, and material-handling systems shall be not less than Class B
11/2-hour-labeled fire doors. Where horizontal conveyors and material-handling
systems penetrate fire-rated walls or smoke partitions, such openings shall be
provided with Class B 11/2-hour-labeled fire doors for two-hour walls and Class
C 3/4-hour-labeled fire doors for one-hour walls or partitions.
m) Thresholds and expansion joint covers
shall be flush with the floor surface to facilitate use of wheelchairs and
carts.
n) Grab bars shall be
provided at all patients' toilets, showers, tubs, and sitz baths. The bars
shall have 11/2-inch clearance to walls and shall have sufficient strength and
anchorage to sustain a concentrated load of 250 pounds.
o) Recessed soap dishes shall be provided at
showers and bathtubs.
p) Location
and arrangement of hand-washing facilities shall permit their proper use and
operation. Particular care shall be given to the clearances required for
blade-type operating handles.
q)
Mirrors shall not be installed at hand-washing fixtures in food preparation
areas or in sensitive areas such as nurseries, clean and sterile supplies, and
scrub sinks.
r) Paper towel
dispensers and waste receptacles (or electric hand dryers) shall be provided at
all hand-washing facilities except scrub sinks.
s) Lavatories and hand-washing facilities
shall be securely anchored to withstand an applied vertical load of not less
than 250 pounds on the front of the fixture.
t) Radiation protection requirements of X-ray
and gamma ray installations shall conform with the National Council on
Radiation Protection and Measurements (NCRP), Report 49: Structural Shielding
Design and Evaluation for Medical Use of X-rays and Gamma Rays of Energies up
to 10 MeV and NCRP Report 102: Medical X-Ray, Electron Beam and Gamma-Ray
Protection for Energies Up to 50 MeV (Equipment Design, Performance and Use).
Provision shall be made for testing the completed installation. All defects
shall be corrected before use.
u)
Ceiling heights shall be as follows:
1) Boiler
rooms shall have ceiling clearances not less than 2 feet, 6 inches above the
main boiler header and connecting piping.
2) Radiographic, operating, and delivery
rooms, and other rooms containing ceiling-mounted equipment or ceiling-mounted
surgical light fixtures, shall have height required to accommodate the
equipment or fixtures.
3) All other
rooms shall have not less than 8-foot ceilings, except that ceilings in
corridors, storage rooms, toilet rooms, and other minor rooms shall be not less
than 7 feet, 8 inches. Suspended tracks, rails, and pipes located in the path
of normal traffic shall be not less than 6 feet, 8 inches above the
floor.
v) Recreation
rooms, exercise rooms, and similar spaces where impact noises may be generated
shall not be located directly over patient bed areas, or delivery or operating
suites, unless special provisions are made to minimize such noise.
w) Rooms containing heat-producing equipment
(such as boiler or heater rooms and laundries) shall be insulated and
ventilated to prevent any floor surface above from exceeding a temperature of
10°F (6°C) above the ambient room temperature.
x) Noise reduction criteria shown in Table B
shall apply to partition, floor, and ceiling construction in patient areas.
(See Table B for sound transmission limitations in general hospitals.) (Table B
is not applicable to existing hospitals.)
y) Elevators. All hospitals having patients'
facilities (such as bedrooms, dining rooms, or recreation areas) or critical
services (such as operating, delivery, diagnostic, or therapy) located on other
than the main entrance floor shall have electric or electrohydraulic elevators.
1) Number of Elevators
A) At least one hospital-type elevator shall
be installed where 1 to 59 patient beds are located on any floor other than the
main entrance floor.
B) At least
two hospital-type elevators shall be installed where 60 to 200 patient beds are
located on floors other than the main entrance floor, or where the inpatient
services are located on a floor other than those containing patient beds.
(Elevator service may be reduced for other floors.)
C) At least three hospital-type elevators
shall be installed where 201 to 350 patient beds are located on floors other
than the main entrance floor, or where the major inpatient services are located
on a floor other than those containing patient beds. (Elevator service may be
reduced for those floors which provide only partial inpatient
services.)
D) For hospitals with
more than 350 beds, the number of elevators shall be determined from a study of
the hospital plan and the estimated vertical transportation
requirements.
2) Cars
and Platforms. Cars of hospital-type elevators shall have dimensions that will
accommodate a patient bed and attendants and shall be at least 5 feet, 8 inches
by 7 feet, 6 inches. The car door shall have a clear opening of not less than 3
feet, 8 inches.
3) Leveling.
Elevators shall be equipped with an automatic leveling device of the two-way
automatic maintaining type with an accuracy of +1/2 inch.
4) Operation. Elevators, except freight
elevators, shall be equipped with a two-way special service key-operated switch
to permit cars to bypass all landing button calls and be dispatched directly to
any floor.
5) Elevator controls,
alarm buttons, and telephones shall be accessible to physically
handicapped.
6) Elevator call
buttons, controls, and door safety stops shall be of a type that will not be
activated by heat or smoke.
7)
Inspections and tests shall be made and written certification shall be
furnished that the installation meets the requirements set forth in this
Section and all applicable NFPA and local codes.
z) Provisions for Natural Disasters
1) General Requirements. An emergency radio
communication system is desirable in each facility. If installed, this system
shall be self-sufficient in a time of emergency and shall also be linked with
the available community system and state emergency medical network system,
including connections with police, fire, and civil defense systems.
2) Earthquakes. In regions where local
experience shows that earthquakes have caused loss of life or extensive
property damage, buildings and structures shall be designed to withstand the
force assumptions specified in the International Building Code. Seismic zones
are identified on the map shown in Illustration A.
3) Tornadoes and Floods. Special provisions
shall be made in the design of buildings in regions where local experience
shows loss of life or damage to buildings resulting from tornadoes or
floods.
Notes
Amended at 35 Ill. Reg. 6386, effective March 31, 2011
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.