Ill. Admin. Code tit. 77, § 265.2850 - Heating, Ventilating and Air-Conditioning Systems (HVAC)
a) General
1) Mechanical System Design
A) Efficiency. The mechanical system shall be
designed for overall efficiency and appropriate life-cycle cost.
i) Recognized engineering procedures shall be
followed for the most economical and effective results.
ii) Client care or safety shall not be
sacrificed for conservation.
iii)
Insofar as practical, the birth center shall include provisions for recovery of
waste cooling and heating energy (ventilation, exhaust, water and steam
discharge, cooling towers, incinerators, etc.).
iv) Use of recognized energy-saving
mechanisms such as variable-air-volume (VAV) systems, and use of natural
ventilation shall be considered, site and climatic conditions
permitting.
v) Birth center design
considerations shall include site, building mass, orientation, configuration,
fenestration, and other features relative to passive and active energy
systems.
B) Air-handling
Systems
i) These shall be designed with an
economizer cycle, where appropriate to use outside air. (Use of mechanically
circulated outside air does not reduce the need for filtration.)
ii) VAV Systems. The energy-saving potential
of variable-air-volume systems is recognized, and the standards in this Section
are intended to maximize appropriate use of those systems. Any system used for
occupied areas shall include provisions to avoid air stagnation in interior
spaces where thermostat demands are met by temperatures of surrounding
areas.
iii) Noncentral air-handling
systems (i.e., individual room units used for heating and cooling purposes,
such as fan-coil units, heat pump units, etc.). These units may be used as
recirculating units only. All outdoor air requirements shall be met by a
separate central air-handling system with proper filtration, as noted in Table
2.1 -3 of the AIA Guidelines.
C) System Valves. Supply and return mains and
risers for cooling, heating, and steam systems shall be equipped with valves to
isolate the various sections of each system. Each piece of equipment shall have
valves at the supply and return ends.
D) Renovation. If system modifications affect
greater than 10 percent of the system capacity, designers shall use
pre-renovation water/air flow rate measurements to verify that sufficient
capacity is available and that renovations have not adversely affected flow
rates in non-renovated areas.
2) Ventilation and Space Conditioning
Requirements. All rooms and areas used for client care shall have provisions
for ventilation.
A) Ventilation Rates. The
ventilation systems shall be designed and balanced, as a minimum, according to
the requirements shown in Table 2.1-2 and the applicable notes of the AIA
Guidelines. The ventilation rates shown in Table 2.1-2 do not preclude the use
of higher, more appropriate rates.
B) Air Change Rates. Air supply and exhaust
in rooms for which no minimum total air change rate is noted may vary down to
zero in response to room load. For rooms listed in Table 2.1-2 of the AIA
Guidelines, where VAV systems are used, minimum total air change shall be
within limits noted.
C) Temperature
and Humidity. Space temperature and relative humidity shall be as indicated in
Table 2.1-2 of the AIA Guidelines.
D) Air Movement Direction. To maintain
asepsis control, airflow supply and exhaust shall generally be controlled to
ensure movement of air from "clean" to "less clean" areas, especially in
critical areas.
E) Mechanical
Ventilation. Although natural ventilation for nonsensitive areas and client
rooms (via operable windows) shall be permitted, mechanical ventilation shall
be considered for all rooms and areas in the birth center.
3) Testing and Documentation
A) Upon completion of the equipment
installation contract, the owner shall be furnished with a complete set of
manufacturers' operating, maintenance, and preventive maintenance instructions,
parts lists, and complete procurement information, including equipment numbers
and descriptions. Required information shall include energy ratings as needed
for future conservation calculations. This information shall be kept by and at
the birth center at all times.
B)
Operating staff persons shall also be provided with written instructions for
proper operation of systems and equipment.
b) Requirements for Specific Locations
1) Birth Rooms
A) Birth room ventilation systems shall
operate at all times, except during maintenance and conditions requiring
shutdown by the building's fire alarm system.
B) During unoccupied hours, birth room air
change rates may be reduced, provided that the positive room pressure is
maintained as required in Table 2.1-2 of the AIA Guidelines.
2) Fuel-fired Equipment Rooms.
Rooms with fuel-fired equipment shall be provided with sufficient outdoor air
to maintain equipment combustion rates and to limit workstation
temperatures.
3) Clean workrooms or
clean holding rooms and soiled workrooms or soiled holding rooms shall comply
with ventilation requirements per Table 2.1-2 of the AIA Guidelines.
c) Thermal Insulation and
Acoustical Provisions. See Section 1.6 -2.2.1 of the AIA Guidelines.
d) HVAC Air Distribution
1) Return Air Systems. For client care areas,
return air shall be by means of
ducted systems.
2) HVAC Ductwork. See Section 1.6-2.2.2.1 of
the AIA Guidelines. Exception: The use of lined ductwork is not permitted to
serve any client area in the birth center.
3) Exhaust Systems - General
A) To enhance the efficiency of recovery
devices required for energy conservation, combined exhaust systems shall be
permitted.
B) Local exhaust systems
shall be used whenever possible in place of dilution ventilation to reduce
exposure to hazardous gases, vapors, fumes, or mists.
C) Fans serving exhaust systems shall be
located at the discharge end and shall be readily serviceable.
4) Air Outlets and Inlets
A) Fresh Air Intakes
i) Fresh air intakes shall be located at
least 25 feet (7.62 meters) from exhaust outlets of ventilating systems,
combustion vents (including those serving rooftop air handling equipment),
medical-surgical vacuum systems, plumbing vents, or areas that may collect
vehicular exhaust or other noxious fumes. (Prevailing winds and/or proximity to
other structures may require greater clearances.)
ii) Plumbing vents that terminate at a level
above the top of the air intake may be located as close as 10 feet (3.05
meters).
iii) The bottom of outdoor
air intakes serving central systems shall be as high as practical, but at least
6 feet (1.83 meters) above ground level, or, if installed above the roof, 3
feet (91.44 centimeters) above roof level.
B) Relief Air. Relief air is exempt from the
25-foot (7.62-meter) separation requirement. Relief air is defined as air that
otherwise could be returned (recirculated) to an air handling unit from the
occupied space, but is being discharged to the outdoors to maintain building
pressure, such as during outside air economizer operation.
C) Gravity Exhaust. Where conditions permit,
gravity exhaust shall be permitted for nonclient areas such as boiler rooms,
central storage, etc.
D)
Construction Requirements. The bottoms of air distribution devices
(supply/return/exhaust) shall be at least 3 inches (7.62 centimeters) above the
floor.
e)
HVAC Filters
1) Filter Efficiencies
A) All central ventilation or air
conditioning systems shall be equipped with filters with efficiencies equal to,
or greater than, those specified in Table 2.1-3 of the AIA
Guidelines.
B) Noncentral
air-handling systems shall be equipped with permanent (cleanable) or
replaceable filters with a minimum efficiency of Minimum Efficiency Reporting
Value (MERV) 3.
C) Filter
efficiencies, tested in accordance with ASHRAE 52.2 (ASHRAE Handbook of
Fundamentals), shall be average.
2) Filter Bed Location. Where two filter beds
are required, filter bed no. 1 shall be located upstream of the air
conditioning equipment and filter bed no. 2 shall be downstream of any fan or
blowers.
3) Filter Frames. Filter
frames shall be durable and proportioned to provide an airtight fit with the
enclosing ductwork. All joints between filter segments and enclosing ductwork
shall have gaskets or seals to provide a positive seal against air
leakage.
4) Filter Housing
Blank-off Panels. Filter housing blank-off panels shall be permanently attached
to the frame and constructed of rigid materials, and shall have sealing
surfaces equal to or greater than the filter media installed in the filter
frame.
5) Filter Manometers. A
manometer shall be installed across each filter bed having a required
efficiency of 75 percent or more, including hoods requiring HEPA filters.
Provisions shall be made to allow access to the manometer for field
testing.
f) Steam and
Hot Water Systems. See Section 1.6-2.2.3 of the AIA Guidelines.