Ill. Admin. Code tit. 77, § 300.3100 - General Building Requirements
a) Elevators
1) Provide a minimum of one elevator in all
buildings of three or more stories in height. Additional elevators shall be
provided as determined by the Department, based on the number, population, and
condition of the residents. The basement, if it is used by residents, shall be
considered as one story.
2) If 60
to 200 beds are located above the second floor, at least one additional
elevator shall be provided. If over 200 beds are located above the second
floor, the number of additional elevators shall be determined by the
Department.
3) The administrator of
the facility must be able to demonstrate to the Department the ability to
transfer a patient according to physician's orders using existing elevators and
elevator doors.
b)
Handrails and Grab Bars
1) Handrails shall be
provided on both sides of all corridors, stairs, and ramps. Handrails shall be
one and one-half inches in diameter and one and one-half inches minimum clear
of the wall. The height shall be 30 to 34 inches measured vertically from floor
surface. Refer to the Rules of the Capital Development Board entitled "Illinois
Accessibility Code" (77 Ill. Adm. Code 400) for other acceptable handrail
dimensions and details. (B)
2) Grab
bars shall be provided at all resident toilets, showers, tubs, and sitz bath.
Refer to the rules of the Capital Development Board entitled "Illinois
Accessibility Code" (71 Ill. Adm. Code 400) for grab bar dimensions and
details. (B)
c) Ceiling
Heights
1) All rooms occupied by or used by
residents shall have not less than eight feet ceiling height.
2) Corridors, storage rooms, toilet rooms and
other minor rooms shall have not be less than seven feet, eight inches ceiling
height.
3) Suspended tracks, rails
and pipes located in the path of traffic shall not be less than six feet, eight
inches above the floor.
d) Doors and Windows
1) Main entrance and exit doors shall swing
outward and be provided with door closers and panic-hardware. (B)
2) All exterior doors shall be equipped with
a signal that will alert the staff if a resident leaves the building. Any
exterior door that is supervised during certain periods may have a disconnect
device for part-time use. If there is constant 24 hour a day supervision of the
door, a signal is not required. (B)
3) Locks installed on resident bedroom doors
shall be so arranged that they can be quickly and easily unlocked from the
corridor side. All such locks shall be arranged to permit exit from the room by
a simple operation without the use of a key. The door may be lockable by the
occupant if the door can be unlocked from the corridor side and the keys are
carried by the attendants at all times. (B)
4) Resident toilet rooms shall open directly
into a corridor or into a resident's bedroom. (B)
5) The doors for the toilet rooms used by
residents shall have a minimum door width of 30 inches. (B)
6) No toilet or bathroom door shall be
provided with hardware which could allow a resident to become locked in the
room. All toilet or bathroom doors and hardware shall be designed to permit
emergency egress from the room. (B)
7) Thresholds or parting strips in doorways
used by residents shall be flush with the floor.
8) Doors and windows shall fit snugly and be
weather tight, and shall open and close easily.
9) Outside doors, other than required exits,
and operable windows shall be equipped with tight-fitting, 16-mesh screens.
Screen doors shall be equipped with self-closing devices.
e) Floors
1) Floors shall be smooth, free from cracks
and finished so that they can be easily and properly cleaned. (B)
2) Floors in bathrooms, kitchens, and utility
rooms shall be completely covered with water resistant material. (B)
f) Walls and Ceilings
1) Walls and ceilings shall have sound
construction, covered with plaster or sheet rock or similar material in good
repair, and free from cracks or holes to permit proper cleaning.
2) Be constructed and maintained so as to
prevent the entrance and harborage of rats, mice, flies, and other
vermin.
g) Exit corridor
walls shall be one hour fire rated construction. Adjoining open spaces shall
not be greater than 600 square feet. Facilities shall provide direct visual
supervision of these open spaces and equip them with an electrically supervised
smoke detection system. (B)
h)
There shall be at least one approved fire extinguisher in all basements,
furnace rooms, and kitchens. In addition, there shall be on each floor of the
building, extinguishers located so a person will not have to travel more than
50 feet from any point to reach one. They shall be inspected annually and
recharged when necessary. The date of checking and recharging shall be recorded
on a tag attached to the extinguisher. (B)
i) Approved containers with proper covers
shall be provided for daily storage of rubbish. (B)
j) Housekeeping throughout the building,
including basements, attics, and unoccupied rooms, shall be adequately
performed to minimize all fire hazards. (B)
k) Facilities shall comply with any
reasonable additional fire protection measures recommended by the Department
over and above these requirements or the Office of the State Fire Marshal if
conditions in and around the building, including its location, indicate that
such additional protection is needed. (B)
l) The building in which a facility is
located shall have no other business that is unrelated to health care and that
constitutes a hazard or annoyance to the residents. The business shall be in a
segregated portion of the building and shall have a separate entrance. (A,
B)