Ill. Admin. Code tit. 77, § 300.3120 - Mechanical Systems
a)
Mechanical systems shall be maintained to assure proper working order and safe
operation. Instructions in the operational use of the systems and equipment
shall be available at the facility.
b) Thermal and Acoustical Insulation.
Insulation shall be provided for the following:
1) Boilers, smoke breeching, and
stacks;
2) Steam supply and
condensate return piping;
3) Hot
water piping above 180 degrees Fahrenheit and all water heaters, generators,
and converters;
4) Hot water piping
above 125 degrees Fahrenheit that is exposed to contact by residents;
5) Chilled water, refrigerant, and other
process piping and equipment operating with fluid temperatures below the
ambient dew point;
6) Water supply
and drainage piping on which condensation may occur;
7) Air ducts and casings with outside surface
temperature below the ambient dew point; and
8) Other piping, ducts, and equipment as
necessary to maintain the efficiency of the system.
c) Insulation may be omitted from hot water
and steam condensate piping that is not subject to contact by residents when
the insulation is not necessary for preventing excessive system heat loss or
excessive heat gain.
d) Insulation
on cold surfaces shall include an exterior vapor barrier.
e) Insulation, including finishes and
adhesives on exterior surfaces of ducts, pipes, and equipment, shall have a
flame spread rating of 25 or less and a smoke developed rating of 50 or less as
determined by an independent testing laboratory in accordance with ASTM
Standard E 84. Exception: Duct, pipe and equipment coverings shall not be
required to meet these requirements if they are located entirely outside of a
building, do not penetrate a wall or roof, or do not create an exposure
hazard.
f) Steam and Hot Water
Systems. Supply and return mains and risers for cooling, heating, and process
steam systems shall be valved to isolate the various sections of each system.
Each piece of equipment shall be valved at the supply and return
ends.
g) Thermal Hazards. Any
surface that is accessible to residents and exceeds a temperature of 140
degrees Fahrenheit (such as radiators, hot water or steam pipes, baseboard
heaters, or therapy equipment) shall be provided with partitions, screens,
shields, or other means to protect residents from injury. Any protective device
shall be designed and installed so that it does not present a fire or safety
hazard or adversely affect the safe operation of the equipment.
h) Heating, Ventilating, and Air Conditioning
Systems
1) Areas of a nursing home used by
residents of the nursing home shall be air conditioned and heated by means of
operable air-conditioning and heating equipment. The areas subject to this
air-conditioning and heating requirement include, without limitation, bedrooms
or common areas such as sitting rooms, activity rooms, living rooms, community
rooms, and dining rooms. (Section 3-202(8) of the Act)
A) The mechanical system shall be capable of
maintaining a temperature of at least 75 degrees Fahrenheit, pursuant to the
requirements of Section
300.670(j).
B) The air-conditioning system shall be
capable of maintaining an ambient air temperature of between 75 degrees
Fahrenheit and 80 degrees Fahrenheit, pursuant to the requirements of Section
300.670(j).
2) Heaters or furnaces of a type
to be installed under, in, or on the floor are not permitted.
3) All ventilation supply, return, and
exhaust systems shall be mechanically operated.
4) The kitchen shall be provided with
ventilation for reasonable comfort, and with sufficient make-up air for the
rangehood exhaust.
5) The laundry
shall be provided with ventilation for reasonable comfort, with air flowing
from clean areas to soiled areas and with exhaust to the outdoors.
6) Outdoor air intakes shall be located as
far as practical, but not less than 15 feet, from the exhaust outlets of
ventilation systems, combustion equipment stacks, plumbing vent stacks, or
areas that may collect vehicular exhaust and other noxious fumes. The bottom of
outdoor air intakes serving central systems shall be located as high as
practical, but not less than six feet above ground level, or, if installed
above the roof, three feet above roof level.
7) Air conditioning and ventilating systems
shall be maintained to comply with the requirements of NFPA 90A.
8) The hood and duct system for cooking
equipment used in processes that produce smoke or grease-laden vapors, such as
griddle frying or deep frying, shall comply with NFPA 96. The hood's
extinguishment system shall be connected to the building fire alarm system and
shall initiate a general alarm when activated. Duct insulation that is used in
lieu of spacing from combustible construction members shall terminate at the
top of the hood on the lower end, covering the duct collar, and shall pass
through any combustible nailer opening in the roof/ceiling assembly and into
the roof jack assembly. The material used shall be installed exactly as the
manufacturer's instructions require.
9) Boiler rooms and other rooms housing
combustion equipment shall be provided with sufficient outdoor air to maintain
proper combustion rates of equipment and to limit room temperatures to 20
degrees Fahrenheit over ambient inside air in adjacent interior spaces. If
sealed combustion units are in use, the discharge line is to remain clear of
any adjacent walk paths and shall be not less than 15 feet from any operable
fenestration or air intakes. NFPA 54 shall apply, including the calculations
for combustion air openings.
10)
For areas within the footprint of the facility that are heated by fuel-fired
appliances using an air-to-air heat exchanger, no fewer than two carbon
monoxide (CO) detectors shall be installed in the area served by each heat
exchanger. One CO detector shall be installed within five feet of a supply duct
and one within five feet of a return or exhaust duct. CO detectors shall be
line or system powered and shall signal the building fire alarm system when
activated. If detectors are line powered, a battery back-up or connection to
the emergency power system is required.