Ill. Admin. Code tit. 77, § 330.3010 - Electrical Drawings
Electrical drawings shall include:
a) All electrically operated systems and
equipment.
b) Electrical service
entrance with service switches, service feeders to the public service feeders,
and characteristics of the light and power current. Transformers and their
connections shall be shown.
c) Plan
and diagram showing main switchboard, power panels, light panels, and
equipment. Feeder and conduit sizes shall be shown with schedule of feeder
breakers or switches.
d) Light
outlets, receptacles, switches, power outlets, and circuits.
e) Telephone layout showing service entrance,
switchboard, strip boxes, outlets, and branch conduit as approved by the
telephone company. Provide separate room and conduits for racks and automatic
switching equipment as required by the telephone company.
f) Fire alarm system with stations, signal
systems, detectors, control board, and wiring diagrams.
g) Emergency electrical system with outlets,
transfer switch, source of supply, feeders, and circuits.