Ill. Admin. Code tit. 77, § 890.1930 - Test Methods
a) Roughed-In
Plumbing. The piping of plumbing drainage and venting systems shall be tested
upon completion of the roughed-in piping installation by water or air to prove
watertight. The Department or local plumbing inspector may require the removal
of any cleanout plugs to ascertain if the pressure has reached all parts of the
system.
b) Water test. The water
test shall be applied to the drainage system either in its entirety or in
sections after piping has been roughed-in. If applied to the entire system, all
openings in the piping shall be tightly closed, except the highest opening, and
the system shall be filled with water to point of overflow. If the system is
tested in sections, each opening shall be tightly plugged except the highest
opening of the section being tested and each section shall be filled with
water; however, a section shall not be tested with less than a ten (10) foot
head of water. In testing successive sections, at least the upper ten (10) feet
of the next higher section shall be tested, so that every joint or pipe in the
building (except the uppermost ten (10) feet of the system) shall be submitted
to a test of at least a ten (10) foot head of water. The water shall be kept in
the system or in the portion being tested for at least 15 minutes before
inspection starts; and inspection or testing of the system shall confirm that
the system is tight at all points.
c) Air test. An air test shall be made by
attaching an air compressor testing apparatus to any suitable opening and after
closing all other inlets and outlets to the system, forcing air into the system
until there is a uniform gauge pressure of five (5) pounds per square inch
(p.s.i.) or sufficient to balance a column of mercury ten (10) inches in
height. This pressure shall be held without introduction of additional air for
a period of at least fifteen (15) minutes.
d) Water Supply System. Upon completion of a
section, or the entire water supply system, the system shall be tested and
proved tight under a water pressure at least one and one-half (1 1/2) times the
system pressure but at least 100 p.s.i., by air or water. When exceeding 100
p.s.i., the test shall be of the hydrostatic type only. Testing pressure shall
be maintained for 15 minutes. The water used for this test shall be from a
potable water supply.
e) Finished
Plumbing. After the plumbing fixtures have been set and their traps filled with
water, their connections shall be tested and proved gas and watertight. The
test for gas and water tightness of the completed drainage and vent system
shall be made by filling all traps with water, and then introducing into the
system a pungent, thick smoke produced by one or more smoke machines. When the
smoke appears at stack openings on the roof, the stack opening shall be closed
and a pressure equivalent to a one (1) inch water column shall be maintained
for the period of the inspection. Where the Department or local plumbing
inspector finds that a smoke test cannot be performed, a peppermint test may be
substituted. A peppermint test is conducted by introducing two (2) ounces of
oil of peppermint into the roof terminal of every line or stack to be tested.
Immediately after the oil of peppermint is introduced into the system, ten (10)
quarts of hot (160 degrees F.) water shall be added, and each terminal sealed.
The detection of the odor of peppermint at any trap or at any other point in
the plumbing system denotes a leak. Individuals whose body or clothing have
come in contact with oil of peppermint shall be excluded from the area until
the test is completed.
f) Building
Sewer. The building sewer shall be tested by insertion of a test plug at the
point of connection with the public sewer. The building sewer shall be filled
with water under a head of at least ten (10) feet of water. The water level at
the top of the water column shall not drop for at least 15 minutes.