Ill. Admin. Code tit. 77, § 905.70 - Buried Sand Filters
a) General.
Buried sand filters may be used, provided that the effluent is discharged in
accordance with the requirements of Section
905.110.
b) Size. Buried sand filters shall be sized
as follows:
1) Residential. The sand filter
surface area for residential property shall be 200 square feet per bedroom.
Where a sand filter is used in conjunction with an approved aerobic treatment
plant, the surface area of the sand filter may be reduced by 50
percent.
2) Non-Residential. All of
the following shall be met when a buried sand filter is to be installed on
non-residential property.
A) The surface area
of the sand filter shall be designed for one square foot per gallon per day for
waste with an influent Biochemical Oxygen Demand (BOD) not to exceed 300 parts
per million (ppm).
B) A sand filter
with flows of 801 gallons or more per day shall have the influent distributed
into the sand filter by a dosing system designed according to subsection (l).
The sand filter shall be dosed 4 times per day with equal flows not to exceed
the design capacity of the filter.
c) A single individual sand filter shall be
used to treat flows from a wastewater source. Splitting flows prior to
treatment or the use of multiple sand filters shall be prohibited unless
subsurface disposal of the effluent is used. Where allowed, splitting of flows
shall be done by pumps.
d) Minimum
Size. The minimum size buried sand filter shall be designed to treat at least
100 gallons of waste per day.
e)
Sand Filter Media. The depth of filter media shall be a minimum of 24 inches.
The sand shall have an effective size of 0.5 to 2.0 millimeters, and a
uniformity coefficient of less than 3.5. It shall be clean and free of clay and
silt.
f) Alternate Media. Other
filter media may be used in a subsurface filter provided that they meet the
criteria of subsection (e) and comply with the following requirements:
1) Are chemically and biologically
inert;
2) Will support biological
growth; and
3) Have a hardness
equivalent to, or greater than, that of sand.
g) Filter Media Cover. The filter media shall
be covered with a minimum of 10 inches of clean coarse gravel or clean stone
that is free of mud, silt or clay, ranging in size from 3/4 to 21/2 inches in
diameter. The gravel or stone shall be covered with straw, untreated building
paper, or other permeable material prior to backfilling. A minimum of 12 inches
of earth cover shall be provided. (See Appendix A, Illustration N.)
h) Distribution and Collection Lines. The
distribution and collection lines shall conform to the requirements for
distribution lines in Section
905.60(b)(2).
The distribution lines shall be level, shall be located 18 inches from
sidewalls, and shall be spaced on 3-foot centers. There shall be solid pipe to
the filter media. The collection lines shall have a slope of 6 inches per 100
feet, and one collection line shall be provided for each 10 feet of width or
fraction of 10 feet, and shall be equally spaced. The upper end of the
collection line shall be capped.
i)
Bedding Material. The bedding material for the collection lines shall be placed
as shown in Appendix A, Illustration N, and shall be clean gravel or clean
stone that is free of mud, silt or clay. The coarse gravel shall range in size
from 3/4 to 21/2 inches in diameter, and pea gravel shall range from 1/8 to 3/8
inches in diameter. A minimum of 2 inches of coarse gravel shall be placed on
the excavation before placement of the collection lines.
j) Venting. A minimum of one vent shall be
placed on the downstream end of the distribution lines as shown in Appendix A,
Illustration N. These vents shall be placed as close as possible to the corners
on the downstream distribution lines. The vents shall extend above the ground
surface and be screened with 1/4- inch mesh screen or equivalent.
k) Drainage. Surface drainage shall be
directed away from the filter. If conditions prohibit gravity drainage of the
filter effluent, a pumping chamber shall be installed. The chamber shall be
constructed of a watertight, non-corrosive material and shall be provided with
a removable lid, which will serve as an access for inspection, cleaning and
general maintenance. An access port or extension collar shall extend at least 6
inches above the ground surface, and the access shall have a minimum dimension
of 12 inches. The chamber shall have sufficient depth and the pump controls
shall be set in a manner to allow for complete drainage of the filter to
eliminate any ponding of effluent within the filter. (See Section
905.125, Pumps, Pumping/Dosing
Chambers, and Ancillary Equipment.)
l) Distribution of Effluent. Buried sand
filters designed to treat non-residential property with flows of 801 gallons or
more per day shall have the effluent distributed into the sand filter by
pumping. The pumps, pumping chamber and ancillary equipment shall comply with
Section 905.125 and the following:
1) Dosing Volume. The dosing volume is the
amount of liquid pumped or siphoned during each cycle minus the amount that
drains back from the sand filter after each dose.
2) Pump Selection. The pump shall be a
submersible pump designed for corrosive liquids.
3) Siphons. Siphons can be designed where
elevation exists between the sand filter and the siphon chamber. However, the
siphon shall be designed to deliver the same flow rate at the same head at the
distribution system as a pump system. The distribution system consisting of
manifold and laterals shall be designed so that it will drain after each
siphon. This shall be accomplished by placing the manifold above the
laterals.