Iowa Admin. Code r. 661-210.3 - General requirements
(1)
Approved single-station smoke alarms shall be acceptable in all areas covered
by this chapter, unless other fire warning equipment or materials are required
by any provision of 661-Chapter 201,202, or 205 or if a fire alarm system with
smoke detection listed under UL 268 has been installed. Any single-station
smoke alarm or multiple-station smoke alarm installed on or after April 1,
2010, in compliance with this subrule, including a replacement of an existing
smoke alarm , shall be listed under UL 217.
(2) Any installation of wiring and equipment
shall comply with 661-Chapter 504.
(3) All devices, combinations of devices, and
equipment to be installed in conformity with this chapter shall be approved and
used for the purposes for which they are intended. Any smoke alarm installed on
or after April 1,2010, in compliance with this chapter, including a replacement
of an existing smoke alarm , shall be listed in accordance with UL 217. Existing
dual sensor smoke alarms may be maintained until replacement is recommended by
the manufacturer or upon failure.
(4) A combination system, such as a household
fire warning system whose components may be used in whole or in part, in common
with a nonfire emergency signaling system, such as a burglar alarm system or an
intercom system, shall not be permitted or approved , except for one- or
two-family dwellings.
(5) All power
supplies shall be sufficient to operate the smoke detector alarm for at least
four continuous minutes.
(6)
Single-station battery-operated or battery backup smoke alarms shall be
replaced in accordance with the manufacturer's instructions.
(7) Power source.
a. In new buildings and additions constructed
after July 1, 1991, required smoke alarms shall receive their primary power
from the building wiring when such wiring is served from a commercial source.
Wiring shall be permanent and without a disconnecting switch other than that
required for overcurrent protection. Smoke alarms may be solely battery-powered
when installed in existing buildings, or in buildings without commercial power,
or in buildings which under go alterations, repairs or additions subject to
subrule 210.3(2).
b. New and
replacement smoke alarms installed after May 1, 1993, which receive their
primary power from the building wiring shall be equipped with a battery
backup.
c. New and replacement
smoke alarms installed after July 1, 2016, which receive their primary power
from the building wiring where more than one smoke alarm is required to be
installed shall be interconnected in such a manner that the activation of one
alarm will activate all of the alarms.
d. After June 30, 2021, a battery-powered
smoke alarm listed in accordance with UL 217 that is newly installed or
replaces an existing battery-powered smoke alarm must be powered by a
nonremovable, nonreplaceable battery that powers the alarm for at least ten
years. The battery requirements of this subrule do not apply to a fire alarm,
smoke detector , smoke alarm , or ancillary component that is electronically
connected as a part of a centrally monitored or supervised alarm system; that
uses a low-power, radio frequency wireless communication signal.
(8) The failure of any nonreliable
or short-life component which renders the alarm inoperative shall be readily
apparent to the occupant of the sleeping unit without the need for a test. Each
smoke alarm shall detect abnormal quantities of smoke that may occur and shall
properly operate in the normal environmental condition.
(9) Equipment shall be installed in
accordance with the manufacturer's recommendations.
(10) Installed fire warning equipment shall
be mounted so as to be supported independently of its attachment to
wires.
(11) All apparatus shall be
restored to normal immediately after each alarm or test.
(12) Smoke alarms shall be located as
follows:
a. On the ceiling or wall outside of
each separate sleeping area in the immediate vicinity of bedrooms.
b. In each room used for sleeping
purposes.
c. In each story within a
dwelling unit, including basements but not including crawl spaces and
uninhabitable attics. In dwellings or dwelling units with split levels and
without an intervening door between the adjacent levels, a smoke alarm
installed on the upper level shall suffice for the adjacent lower level
provided that the lower level is less than one full story below the upper
level.