Kan. Admin. Regs. § 26-40-304 - Nursing facility physical environment; details and finishes
Each nursing facility shall incorporate details and finishes to create a home environment.
(a) Codes
and standards. Nursing facilities may be subject to codes, standards, and
regulations of several different jurisdictions, including local, state, and
federal authorities. The requirements in this regulation shall be considered as
a minimum. Each nursing facility and each portion of a nursing facility that
was licensed under a previous regulation shall, at a minimum, remain in
compliance with the regulation or building code in effect at the date of
licensure. Each applicant for a nursing facility license and each addition to a
nursing facility licensed on or after the effective date of this regulation
shall meet the following requirements, as adopted by reference in K.A.R.
26-39-105:
(1) The "international building
code" (IBC);
(2) the national fire
protection association's NFPA 101 "life safety code" (LSC); and
(3) the "Americans with disabilities act
accessibility guidelines for buildings and facilities" (ADAAG).
(b) Details.
(1) Corridors.
(A) The width of each corridor shall be at
least eight feet in any resident-use area and at least six feet in any nursing
facility support area.
(B)
Handrails shall not be considered an obstruction when measuring the width of
corridors.
(C) Doors shall not
swing directly into corridors, with the exception of doors to small closets and
spaces that are not subject to occupancy. Walk-in closets shall be considered
occupiable spaces.
(2)
Ceiling height.
(A) The height of each ceiling
shall be at least eight feet above the finished floor with the following
exceptions:
(i) Each ceiling in a storage room
or other normally unoccupied space shall be at least seven feet eight inches
above the finished floor.
(ii) Each
ceiling in a room containing ceiling-mounted equipment shall have sufficient
height to accommodate the proper functioning, repair, and servicing of the
equipment.
(B) Each
building component and suspended track, rail, and pipe located in the path of
normal traffic shall be at least six feet eight inches above the finished
floor.
(C) Each architecturally
framed and trimmed doorway or other opening in a corridor or room shall have a
height of at least six feet eight inches above the finished floor.
(3) Doors and door hardware.
(A) Each door on any opening between
corridors and spaces subject to occupancy, with the exception of elevator
doors, shall be swinging-type.
(B)
Each door to a room containing at least one resident-use toilet, bathtub, or
shower shall be swinging-type, sliding, or folding and shall be capable of
opening outward or designed to allow ingress to the room without pushing
against a resident who could have collapsed in the room.
(C) The width of the door opening to each
room that staff need to access with beds or stretchers shall be at least three
feet eight inches. The width of each door to a resident-use toilet room and
other rooms that staff and residents need to access with wheelchairs shall be
at least three feet.
(D) No more
than five percent of the resident rooms may have a Dutch door to the corridor
for physician-ordered monitoring of a resident who is disorientated.
(E) Each exterior door that can be left in an
open position shall have insect screens.
(F) Each resident-use interior and exterior
door shall open with ease and little resistance.
(G) Each resident-use swinging-type door
shall have lever hardware or sensors for ease of use by residents with mobility
limitations.
(4)
Glazing. Safety glazing materials shall be required in all doors with glass
panels, sidelights, and any breakable material located within 18 inches of the
floor. Safety glass or safety glazing materials shall be used on any breakable
material used for a bath enclosure or shower door.
(5) Windows.
(A) Each window in a resident's room or in a
resident-use area shall have a sill located no greater than 32 inches above the
finished floor and at least two feet six inches above the exterior grade. This
paragraph shall not apply if the building was constructed and licensed as a
nursing facility before February 15, 1977. If the building was constructed and
licensed as a nursing facility on or after February 15, 1977 and before
November 1, 1993, the nursing facility shall have a windowsill height three
feet or less above the floor in the living and dining areas for at least 50
percent of the total window area.
(B) Each window in a resident's room shall be
operable.
(C) Each operable window
shall have an insect screen.
(D)
Each operable window shall be designed to prevent falls when open or shall be
equipped with a security screen.
(E) Blinds, sheers, or other
resident-controlled window treatments shall be provided throughout each
resident unit to control light levels and glare.
(6) Grab bars.
(A) Grab bars shall be installed at each
resident-use toilet and in each shower and tub.
(B) Each wall-mounted grab bar shall have a
clearance of 11/2 inches from the wall.
(C) Each grab bar, including those molded
into a sink counter, shall have strength to sustain a concentrated load of 250
pounds.
(D) Permanent or flip-down
grab bars that are 11/2 inches in diameter shall be installed on any two sides
of each resident-use toilet, or the resident-use toilet shall have at least one
permanent grab bar mounted horizontally at least 33 inches and no more than 36
inches above the floor and slanted at an angle.
(E) The ends of each grab bar shall return to
the wall or floor.
(F) Each grab
bar shall have a finish color that contrasts with that of the adjacent wall
surface.
(7) Handrails.
(A) Each handrail shall be accessible
according to ADAAG, as adopted by reference in K.A.R. 26-39-105 . Alternative
cross sections and configurations that support senior mobility shall be
permitted.
(B) Each stairway and
ramp shall have handrails.
(C) A
handrail shall be provided for each resident-use corridor with a wall length
greater than 12 inches.
(D) Each
handrail shall have a clearance of 11/2 inches from
the wall.
(E) The ends of each
handrail shall return to the wall.
(F) Each handrail and fastener shall be
completely smooth and free of rough edges.
(8) Heated surfaces.
(A) Each heated surface in excess of
100°F with which a resident may have contact shall be insulated and covered
to protect the resident.
(B) If
heated surfaces, including cook tops, ovens, and steam tables, are used in
resident areas, emergency shut-offs shall be provided.
(9) Hand-washing stations.
(A) The water supply spouts for each sink
shall be sensor-operated or operable with one hand and shall not require tight
grasping, pinching, or twisting of the wrist.
(B) The water supply spout at each sink
located in the resident unit and any other areas available for resident use
shall be mounted so that the discharge point is at least five inches above the
rim of the fixture.
(C) An enclosed
single-issue paper towel dispenser or mechanical hand-drying device shall be
provided at each hand-washing sink.
(D) A wastebasket shall be located at each
hand-washing sink.
(E) A mirror
shall be placed at each hand-washing sink located in a resident room, a
resident toilet room, and a bathing room and in each public toilet room. The
placement of the mirror shall allow for convenient use by both a person who
uses a wheelchair and a person who is ambulatory. The bottom edge of each
mirror shall be no more than 40 inches from floor level.
(10) Lighting.
(A) All interior and exterior nursing
facility lighting shall be designed to reduce glare.
(B) Each space occupied by persons,
machinery, equipment within the nursing facility, and approaches to the nursing
facility and parking lots shall have lighting.
(C) Each corridor and stairway shall remain
lighted at all times.
(D) Each
resident room shall have general lighting and night lighting. The nursing
facility shall have a reading light for each resident. At least one light
fixture for night lighting shall be switched at the entrance to each resident's
room. All switches for the control of lighting in resident areas shall be of
the quiet-operating type.
(E) Each
light located in a resident-use area shall be equipped with a shade, globe,
grid, or glass panel.
(F) Each
light fixture in wet areas, including kitchens and showers, shall be
vapor-resistant and shall have cleanable, shatter-resistant lenses and no
exposed lamps.
(c) Finishes.
(1) Flooring.
(A) Each floor surface shall be easily
cleaned and maintained for the location.
(B) If the area is subject to frequent
wet-cleaning methods, the floor surface shall not be physically affected by
germicidal or other types of cleaning solutions.
(C) Each floor surface, including tile joints
used in areas for food preparation or food assembly, shall be water-resistant,
greaseproof, and resistant to food acids. Floor construction in dietary and
food preparation areas shall be free of spaces that can harbor rodents and
insects.
(D) Each flooring surface,
including wet areas in kitchens, showers, and bath areas, entries from exterior
to interior spaces, and stairways and ramps, shall have slip-resistant
surfaces.
(E) All floor
construction and joints of structural elements that have openings for pipes,
ducts, and conduits shall be tightly sealed to prevent entry of rodents and
insects.
(F) Highly polished
flooring or flooring finishes that create glare shall be avoided.
(G) Each flooring surface shall allow for
ease of am-bulation and movement of all wheeled equipment used by residents or
staff and shall provide for smooth transitions between differing floor
surfaces.
(H) Each threshold and
expansion joint shall be designed to accommodate rolling traffic and prevent
tripping.
(I) Each carpet and
carpet with padding in all resident-use areas shall be glued down or stretched
taut and free of loose edges or wrinkles to avoid hazards or interference with
the operation of lifts, wheelchairs, walkers, wheeled carts, and residents
utilizing orthotic devices.
(2) Walls, wall bases, and wall protection.
(A) Each wall finish shall be washable and,
if located near plumbing fixtures, shall be smooth and
moisture-resistant.
(B) Wall
protection and corner guards shall be durable and scrubbable.
(C) Each wall base in areas that require
frequent wet cleaning, including kitchens, clean and soiled workrooms, and
housekeeping rooms, shall be continuous and coved with the floor, tightly
sealed to the wall, and constructed without voids that can harbor rodents and
insects.
(D) All wall construction,
finish, and trim in dietary and food storage areas shall be free from spaces
that can harbor rodents, insects, and moisture.
(E) Each wall opening for pipes, ducts, and
conduits and the joints of structural elements shall be tightly sealed to
prevent entry of rodents and insects.
(F) Highly polished walls or wall finishes
that create glare shall be avoided.
(3) Ceilings.
(A) The finish of each ceiling in
resident-use areas and staff work areas shall be easily cleanable.
(B) Each ceiling in dietary, food
preparation, food assembly, and food storage areas shall have a finished
ceiling covering all overhead pipes and ducts. The ceiling finish shall be
washable or easily cleaned by dustless methods, including vacuum
cleaning.
(C) Each ceiling opening
for pipes, ducts, and conduits and all joints of structural elements shall be
tightly sealed to prevent entry of rodents and insects.
(D) Impervious ceiling finishes that are
easily cleaned shall be provided in each soiled workroom, housekeeping room,
and bathing room.
(E) Finished
ceilings may be omitted in mechanical and equipment spaces, shops, general
storage areas, and similar spaces unless required for fire protection.