02-658 C.M.R. ch. 11, § 7 - Piping, Pumps and Valves
11.7.1
Supply
Connections
11.7.1.1 A listed lever or
wheel, thermally-operated oil shut-off valve designed to shut off the oil
supply in case of fire, must be installed at the burner and at the oil supply
tank.
11.7.1.1.1 When outside tanks are used,
a thermally operated shut-off valve must be installed where the supply line
enters (inside) the building.
11.7.1.1.2 When inside tanks are used and the
oil supply tank is installed in a separate room, a thermally operated shut-off
valve shall be installed where the line enters the room where the appliance is
located.
11.7.1.2
Whenever the oil supply is taken from the top of an oil tank, whether the oil
tanks are outside or inside, a thermally operated wheel or lever type shut-off
valve must be installed at the tank and at the burner for control of the fuel.
A check valve may be used in the supply line, but no valve or obstruction shall
be placed in a return line connected to a burner or pump.
11.7.2
Thermally-Operated Valves
Thermally operated valves over 1/2 inch that are not currently listed may be installed upon receipt of written approval of a Board inspector. The written approval must be requested and received prior to installation.