02-658 C.M.R. ch. 110, § 17 - Safety and Pressure Relief Valves
1. Steam and
hot water boilers shall be equipped with listed or approved steam safety or
pressure relief valves that conform to ASME requirements. A shut-off valve may
not be placed between the relief valve and the boiler or on discharge pipes
between such valves and the atmosphere.
2. All steam safety or pressure relief valves
shall terminate in a manner which precludes the possibility of accidental
scalding in accordance with ASME.
3. Steam safety or pressure relief valves
which terminate in the structure shall terminate 6" to 12" above the
floor.
4. No valves or other
obstructive devices may be installed between the boiler and any safety controls
or devices.