02-658 C.M.R. ch. 8, § 9 - Oil Supply Tanks
Rectangular built-in place tanks shall be fabricated using one-quarter (1/4) inch minimum thick steel sheets reinforced on maximum 24-inch centers. Tank bottoms must be supported on 12-inch-wide non-combustible piers, to a height of 8 inches above the floor. All welding must be performed by a welder. Tanks must be designed by a registered engineer who shall observe the tank under 5 PSI test and certify to it being tight under this test.
All fuel oil supply tanks must be a minimum of five (5) feet from any gas and/or solid fuel burning appliance.
If an oil burning appliance is converted to an alternative fuel, but the tank is left in place so that it can be returned to service at some future date, all of the following requirements must be met before the alternative fuel is used:
Oil can remain in the tank unless prohibited by the local Authority Having Jurisdiction or the Maine Department of Environment Protection.
If a fuel supply tank is permanently removed from service for whatever reason, the tank and all piping connected to it, including the outside fill and vent piping and any supply piping connected to the appliance, shall be: