02-658 C.M.R. ch. 9, § 12 - Electrical Wiring and Equipment
9.12.1
Basic Standards
The following standards must be met for the electrical wiring and equipment used in connection with solid fuel burning equipment:
9.12.1.1 The electrical wiring and equipment
used must be installed in accordance with NFPA 70.
9.12.1.2 Safety control circuits must be
two-wire, one side grounded, having a nominal voltage not exceeding 150 Volts.
A safety control or protective device must be connected so as to interrupt the
ungrounded conductor; and
9.12.1.3
The control circuit must be connected to a power supply branch circuit fused at
not more than the value appropriate for the rating of any control or device
included in the circuit.
9.12.2
Additional Standards: Automatic
Feed
The following additional standards must be met for solid fuel burning appliances where the fuel is automatically fed:
9.12.2.1
Electrical Equipment, Required
Control Switches
9.12.2.1.1
Thermal Electric Switches. A thermal cut-off switch must be wired
into the burner circuit to shut off the burner in the event of a fire at the
unit. The switch must be placed directly above the unit to be fired with the
thermal element pointed downwards and must be placed at the front of the unit.
The switch must be no lower than the highest point of the flue connector where
it enters the chimney. The switch must be wired to shut-off the burner,
circulating fan, forced or induced draft fan and any remote fuel delivery
device that is not an integral part of the burner. A thermal electric switch is
required for each unit in a multi-appliance installation.
9.12.2.1.2 On multi-appliance installations
the emergency and thermal electrical switches must be wired in series through
individual unit relays such that, if one thermal switch or the "EMERGENCY"
switch is open, the combustion air fan and fuel delivery system will be shut
off. This also applies if there are two or more appliance rooms in the same
building connected to a common fuel supply system.
[NOTE: An example of wiring for multi-appliance installations is illustrated in Figure 9-2.]
Click to view image
9.12.2.2
Disconnect Switch. A
burner disconnect switch must be placed within three (3) feet of the
burner.
9.12.2.3
Emergency
Switch
9.12.2.3.1 An identified switch
to shut down the boiler, furnace or water heater in an emergency must be placed
outside of and adjacent to the entrance to the room where the appliance is
located.
9.12.2.3.2 If the entrance
to the room where the appliance is located is only accessible from outdoors,
the emergency switch may be placed inside not more than one (1) foot beyond the
door opening.