When an appliance is converted from a liquid or gaseous fuel
to a solid fuel, the conversion burner must be listed by Underwriters'
Laboratory or by an independent nationally recognized testing laboratory and
must comply with all Sections of this Chapter.
9.14.1
Testing in Individual
Appliance Required
A conversion burner must be tested for use in the individual
appliance in which it is intended to be installed and must meet one of the
following conditions:
1. The
conversion burner has been tested by the burner manufacturer in the individual
appliance in which it is intended to be installed and has been approved for use
in such appliance by a licensed professional engineer with the proper
disciplines;
2. The conversion
burner has been tested by an independent testing laboratory in the individual
appliance in which it is intended to be installed and has been certified for
use in such appliance by the independent testing laboratory; or
3. The conversion burner has been tested by
the appliance manufacturer in the individual appliance in which it is intended
to be installed and has been approved for use in such appliance by the
appliance manufacturer.
Such appliance manufacturer or licensed professional engineer
must provide installation and combustion set-up instructions for the
appliance.
9.14.2
Installation into Direct Vent
Appliances
A conversion burner shall not be installed into direct vent
appliances unless the conversion burner has been approved for use in the
appliance by the manufacturer of the appliance.
9.14.3
Installation into Power Vented
Appliances
A conversion burner shall not be installed into power vented
appliances unless the power venter is specifically approved for use with solid
fuel.
9.14.4
Conversion From Another Fuel Source
When converting to solid fuel from another fuel source, the
installation must comply with all applicable provisions of NFPA 211 and the
Board's Rules.
9.14.5
Clearance From Combustible Materials Required
Warm air furnace plenums and ductwork must comply with the
applicable provisions of NFPA 90B for clearance from combustible
materials.
9.14.6
Oil
Tank Requirements upon Conversion to Solid Fuel
9.14.6.1 If an oil burning appliance is
converted to an alternative fuel, but the tank is left in place so that it can
be returned to service at some future date, all of the following requirements
must be met before the alternative fuel is used:
9.14.6.1.1 The vent piping must remain intact
and open to the outside of the building;
9.14.6.1.2 The fill pipe must be removed
completely and the tank must be plugged with a threaded malleable iron
plug;
9.14.6.1.3 The burner supply
line must be removed and the valves on both the tank and burner must be capped
or plugged;
9.14.6.2 If
an underground oil supply line is in use and complies with Section 8.8 of these
rules, it may remain in place provided that all of the following conditions are
met:
1. The oil line is emptied of its
contents;
2. The oil line is
disconnected from the oil tank and burner; and
3. The oil line is plugged on both ends in
addition to the burner and tank fittings being plugged.
9.14.6.3 Oil can remain in the tank unless
prohibited by the local authority having jurisdiction or the Department of
Environment Protection.
9.14.6.4
The requirements of this section must be performed by a master or journeyman
Oil Burner Technician.
9.14.7
Interlock Device Required
An interlock device must be installed so that combustion will
be arrested if the burner is removed from the heating appliance.
9.14.8
Limited Control
Required
Furnaces must have a 250 degree Fahrenheit limit control
installed in the supply plenum not more than 10" above the top surface of the
heat exchanger. The limit control shall extend at least 12" into the supply
plenum.