225 CMR, § 22, ch. 4, § R405 - TOTAL BUILDING PERFORMANCE
R405 Replace Section R405 in its entirety as follows:
Section R405 Passive House Building Certification Option.
R405.1
Compliance. Projects may document compliance with either Phius
certification in accordance with R405.2.1 or PHI certification in accordance
with R405.2.2 or follow R405.3. Buildings shall be pre-certified as meeting the
Phius CORE 2021 or Phius ZERO 2021 Passive Building Standard - North America,
or newer, demonstrated using approved Passive House certification software and
program criteria by PHIUS, where design-certification is demonstrated by Phius
and a Certified Passive House Consultant (CPHC); or, Projects meeting the
Certified Passive House standard using the approved Passive House certification
software and program criteria by the Passive House Institute (PHI), where PHI
certification is demonstrated by a PHI-accredited Certifier.
R405.2
Documentation. Compliance
with Phius or PHI shall be in accordance with R405.2.1 or R405.2.2.
1. Prior to the issuance of a building
permit, the following item(s) must be provided to the Building Official:
a. A Passive House Verification report with
results from the approved Passive House certification software which
demonstrates project compliance with Phius CORE 2021 (or newer), or Phius ZERO
2021 (or newer) performance requirements.
b. A statement from the CPHC that the
verification report results accurately reflect the plans submitted.
c. Evidence of project registration from
Phius.
OR
a. A
Design Certification Letter from Phius.
2. Prior to the issuance of a final
certificate of occupancy, the following item(s) must be provided to the
building official:
a. Design Certification
Letter from Phius.
b. An updated
Passive House Verification Report with results from the approved Passive House
certification software which reflects "as-built" conditions and test results
(blower door and ventilation results) that demonstrate project compliance with
Phius performance requirements.
c.
A statement from the CPHD Certified Passive House Consultant or Certified
Passive House Designer that the project test results meet the model performance
requirements, all the mandatory limits and any other mandatory
requirements.
d. A copy of the
Passive House Verifier/Rater's test results;
e. A copy of the Phius workbook listing all
testing results and as-built conditions.
OR
a. A
Final Certification Letter, provided by Phius.
AND
f.
Verification of compliance with R404.4 EV ready, and Appendix RB: Solar Ready
Provisions.
R405.2.2
Passive House Institute (PHI) Documentation.
1. Prior to the issuance of a building
permit, the following items must be provided to the Building Official:
a. A PHPP (Passive House Planning Package)
compliance report with results from the approved Passive House certification
software which demonstrates project compliance with current PHI performance
requirements;
b. A statement from
the PHI-accredited Certifier that the approved Passive House certification
software results and compliance report accurately reflect the plans
submitted;
c. Evidence of project
registration from a PHI-accredited Certifier.
OR
a. A
Design State Conditional Assurance Letter from a PHI-accredited
Certifier.
2. Prior to
the issuance of a final certificate of occupancy, the following items must be
provided to the building official:
a. A Design
State Conditional Assurance Letter from a PHI-accredited Certifier.
b. An updated compliance report with results
from the approved Passive House certification software which reflects
"as-built" conditions and test results (blower door and ventilation results)
that demonstrates project compliance with PHI performance requirements;
c. A statement from the Certified
Passive House Consultant or Certified Passive House Designer that the project
test results meet the model performance requirements, all the mandatory limits
and any other mandatory requirements.
d. A copy of the Passive House
Verifier/Rater's test results;
OR
a. A
Final Certification Letter from a PHI-accredited Certifier.
AND
e.
Verification of compliance with R404.4 EV ready, and Appendix RB: Solar Read
Provisions.
R405.3
Documentation of projects that
pursued Phius or PHI certification that did not achieve final
certification.
R405.3.1
Compliance. Buildings shall be pre-certified per Section R405.1.
If, at construction completion, final certification cannot be received from
either Phius or PHI, this compliance pathway may be followed to receive a
certificate of occupancy based on compliance with R405.3.2 Documentation.
Compliance via R405.3.2 is not equivalent to either Phius or PHI Certification
and will not designate the project as a certified passive house.
R405.3.2
Near Passive House
Documentation. The following materials are required:
a. Statement from the Phius certified
consultant or PHI-accredited verifier confirming project has completed all
interim, final, and corrective testing and modeling requirements, including a
summary of deviations from certification requirements.
b. Copy of executed contracts with Phius
consultant or PHI rater/verifier covering all required inspections and testing
requirements for certification.
c.
Design phase pre-certification/approval, in the form of a statement issued from
Phius or PHI-accredited verifier confirming design certification or
pre-certification was achieved.
d.
Report from rater/verifier demonstrating as-built conditions, including those
that comply with Phius or PHI requirements, and those that do not.
i. If the initial whole building blower door
tests do not meet the Phius or PHI airtightness requirement, a statement must
be provided to reflect evidence of a re-test. Statement shall include an
explanation for sources of leakage and attempted remediation efforts. Final
test results shall not exceed Phius or PHI airtightness thresholds by more than
30%.
ii. If the mechanical
ventilation flow rates and balance do not meet the requirements of Phius or
PHI, report must show that installed ventilation system demonstrates compliance
with the mechanical code in accordance with Section C403.
e. For projects with Phius design
certification, provide final Energy Star and Zero Energy Ready Homes
certificates.
f. A letter from a
licensed professional engineer that states that the potential hygrothermal or
moisture risk of the as-built assemblies, with the measured blower door test
result, is acceptably low.