780 CMR, CHAPTER 51, ch. R5, R506 - Allowable joist spans
Add new section R506.1.1 Control Joints as follows:
Exception: Control joints may be omitted when the slab is reinforced in accordance with Table R506.1.1. Reinforcement shall be placed at the mid-depth of the slab or two inches (51 mm) from the top of slabs greater than 4 inches (102 mm) in thickness.
Add new Table R506.1.1 as follows:
Table R506.1.1
|
MAXIMUM DIMENSION OF SLAB OR DISTANCE BETWEEN CONTROL JOINTS (ft.) |
WWF WIRE |
WWF WIRE SIZE |
|||||
|
Slab Thickness (in.) |
|||||||
|
3.5 |
4.0 |
4.5 |
5.0 |
5.5 |
6.0 |
||
|
42 |
36 |
32 |
29 |
26 |
24 |
6 x 6 |
W1.4 x W1.4 |
|
59 |
52 |
46 |
42 |
38 |
35 |
6 x 6 |
W2.0 x W2.0 |
|
86 |
75 |
67 |
60 |
55 |
50 |
6 x 6 |
W2.9 x W2.9 |