Rule 9. Sections 3.3.64, 4.6.10.1, 4.7.4, 4.8.2.2, 6.2.1.2,
7.2.1.12, 8.3.5, 8.3.5.5.1, 8.3.6.1, 8.4.2,8.4.5.1, 8.5.7.1,
8.6.10.2.1,
8.7.3.1, 9.1.1, 9.4.2.1, 9.4.2.2, 9.6.3.5.5, 12.3.2.1.2, 12.7.6.1, 13.3.2.1.2,
13.7.6.1 and 43.1.2.1 of the code adopted by reference in
R
29.2002 are amended, section 8.6.10.2.1.1 is added,
and sections 7.2.1.12.1, 7.2.1.12.2, 7.3.3.2, 9.1.2, 9.4.3.1, 9.4.3.2,
12.2.10.3, 12.2.11.2, 12.7.1.3, 12.7.6.2, 12.7.7.2, 12.7.9.3.1, 12.7.9.3.2,
12.7.9.3.3, 13.2.10.3, 13.2.11.2, 13.7.1.3, 13.7.6.2, 13.7.7.2, 13.7.9.3.1,
13.7.9.3.2, 13.7.9.3.3, and 43.1.4.5 of the code are deleted, as
follows:
3.3.64 Dormitory. A building
or a space in a building in which group sleeping accommodations are provided
for more than 16 persons who are not members of the same family in 1 room, or a
series of closely associated rooms, under the control of the school authority,
with or without meals, but without individual cooking facilities.
4.6.10.1. Buildings or portions of buildings
shall be permitted to be occupied during construction, repair, alterations, or
additions only where all required means of egress and required fire protection
features in the building and on-site are in place and continuously maintained
for the portion occupied and if the occupied portion is separated from the part
under construction by a fire barrier that has a 1-hour-fire-resistance rating.
The temporary 1-hour-rated fire barrier that is used for separation may be
constructed of combustible material. Instead of having all required means of
egress and fire protection features in place, the school authority or
designated representative may take other measures that would provide equivalent
safety if approved by the bureau of fire services.
4.7.4. Drills shall be held at various times
under varying conditions to simulate the unusual conditions that may occur in
an actual emergency.
4.8.2.2. The
school authority or designated representative shall submit the required
emergency plans to the bureau of fire services upon request for
review.
6.2.1.2. Hazard of contents
shall be classified by the registered design professional (rdp) or owner and
upon request shall be submitted to the authority having jurisdiction for review
and approval on the basis of character of the contents and the processes of
operations conducted in the building or structure.
7.2.1.12. Where permanently mounted folding
or movable partitions divide a room into smaller spaces, a swinging door leaf
or open doorway shall be provided as an exit access from each space.
7.2.1.12.1. Deleted.
7.2.1.12.2. Deleted.
7.3.3.2. Deleted.
8.3.5. The provisions of section
8.3.5
shall govern the materials and methods of construction used to protect
through-penetration and membrane penetrations in fire walls, fire barrier
walls, and fire resistance-rated horizontal assemblies. The provisions of
section
8.3.5
shall not apply to existing material and methods of construction used to
protect existing through-penetrations and existing membrane penetrations in
fire walls, fire barrier walls, or fire resistance-rated horizontal assemblies,
unless otherwise required by chapters 11 to 43.
8.3.5.5.1. Where piping penetrates a fire
resistance-rated wall or floor assembly, combustible piping shall not connect
to noncombustible piping within 35 inches (915 millimeters) of the fire stop
system or device with the demonstration that the transition will not reduce the
fire resistance rating, except in the case of existing
installations.
8.3.6.1.
The provisions of section 8.3.6 shall govern the materials and methods of
construction used to protect joints in between and at the perimeter of fire
barriers or, where fire barriers meet other fire barriers, the floor or roof
deck above, or the outside walls. The provisions of section 8.3.6 shall not
apply to existing materials and methods of construction used to protect
existing joints in fire barriers, unless otherwise required by chapters 11 to
43.
8.4.2. Smoke partitions shall
comply with the following:
(1) They shall
extend from the floor to the underside of the floor or roof deck above, through
any concealed spaces, such as those above suspended ceilings, and through
interstitial structural and mechanical spaces.
(2) They shall be permitted to extend from
the floor to the underside of a monolithic or suspended ceiling where all of
the following conditions are met:
(a) The
ceiling system forms a continuous membrane.
(b) A smoke-tight joint is provided between
the top of the smoke partition and the bottom of the suspended
ceiling.
(c) Where the space above
the ceiling is used as a plenum, air transfer openings in smoke partitions into
the plenum shall be provided with approved smoke dampers designed and tested in
accordance with the requirements of ANSI/UL 555S, standard for smoke dampers,
to limit the transfer of smoke.
(3) Smoke partitions enclosing hazardous
areas shall be permitted to terminate at the underside of a monolithic or
suspend ceiling where the following conditions are met:
(a) The ceiling system forms a continuous
membrane.
(b) A smoke-tight joint
is provided between the top of the smoke partition and the bottom of the
suspended ceiling.
(c) Where the
space above the ceiling is used as a plenum, air transfer openings in smoke
partitions into the plenum shall be provided with approved smoke dampers
designed and tested in accordance with the requirements of ANSI/UL 555S,
standard for smoke dampers, to limit the transfer of smoke.
8.4.5.1. The provisions
of section 8.4.5 shall govern the materials and methods of construction used to
protect joints in between and at the perimeter of smoke partitions or, where
smoke partitions meet other smoke partitions, the floor or roof deck above or,
the outside walls. The provisions of section 8.4.5 shall not apply to existing
materials and methods of construction used to protect existing joints in smoke
partitions, unless otherwise required by chapters 11 to 43.
8.5.7.1. The provisions of section 8.5.7
shall govern the materials and methods of construction used to protect joints
in between and at the perimeter of smoke barriers, or where barriers meet other
smoke barriers, the floor or roof deck above, or the outside walls.
8.6.10.2.1. Unless otherwise provided in
section 8.6.10.2.1.1, the aggregate area of a mezzanine located within a room,
other than those located in a special-purpose industrial occupancies, shall not
exceed one-third the open area of the room in which the mezzanines are located.
Enclosed spaces shall not be included in a determination of the size of the
room in which the mezzanine is located.
8.6.10.2.1.1. The aggregate area of
mezzanines in buildings and structures of type I or type II construction shall
not exceed one-half of the floor area of the room in buildings and structures
equipped throughout with an approved automatic sprinkler system in accordance
with section 9.7 and an approved emergency voice or emergency alarm
communication system pursuant to NFPA 72.
8.7.3.1. The school authority or designated
representative shall store and handle flammable and combustible liquids in
compliance with R 29.5101 to R 29.5516 promulgated by the Michigan department
of licensing and regulatory affairs, bureau of fire services under the
provisions of the act.
9.1.1. The
school authority or designated representative shall ensure the equipment which
utilizes gas and related gas piping is installed in compliance with the
provisions of NFPA 54, national fuel gas code, NFPA 58, liquefied petroleum gas
code, or rules promulgated under the act, as applicable.
9.1.2. Deleted.
9.4.2.1. The school authority or designated
representative shall ensure that new elevators, escalators, dumbwaiters, and
moving walks are installed in compliance with the elevator rules,
R
408.7001 to
R 408.7103.
9.4.2.2. The school authority or designated
representative shall ensure that existing elevators, escalators, dumbwaiters,
and moving walks are in compliance with the Michigan elevator rules,
R
408.7001 to
R 408.7103.
9.4.3.1. Deleted.
9.4.3.2. Deleted.
9.6.3.5.5. Visible signals shall not be
required in any of the following:
(1) Exit
stair enclosures.
(2) Offices less
than 200 square feet.
(3) Closets
and coat rooms.
(4) Electrical
closets.
(5) Mechanical pipe
chases.
(6) Crawl spaces.
(7) Small bathrooms in classrooms.
(8) Janitor closets.
(9) Storage rooms less than 200 square
feet.
(10) Unoccupied spaces.
12.2.10.3.
Deleted.
12.2.11.2.
Deleted.
12.3.2.1.2. Rooms or spaces
for the storage, processing, or use of materials specified in section
12.3.2.1.2(1) to (3) shall be protected pursuant to all of the following:
(1) Separation from the remainder of the
building by fire barriers having a minimum 1-hour fire resistance rating or
protection of such rooms by automatic extinguishing systems as specified in
section
8.7
in the following areas:
(a) Boiler and
furnace rooms, unless otherwise permitted by either of the following:
(i) The requirement of section
12.3.2.1.2(1)(a) shall not apply to rooms enclosing furnaces, heating and
air-handling equipment, or compressor equipment with a total aggregate input
rating less than 200,000 BTU (211MJ), provided that such rooms are not used for
storage.
(ii) The requirement of
section 12.3.2.1.2(1)(a) shall not apply to attic locations of the rooms
addressed in section 12.3.2.1.2(1)(a)(i), provided that such rooms comply with
the draft stopping requirements of section
8.6.10.
(b) Rooms or spaces larger than
100 square feet (4.6 square meters) and used for the storage of combustible
supplies.
(c) Rooms or spaces used
for the storage of hazardous materials or flammable or combustible liquids in
quantities deemed hazardous by recognized standards.
(2) Separation from the remainder of the
building by fire barriers having a minimum 1-hour fire resistance rating and
protection of such rooms by automatic extinguishing systems as specified in
section
8.7
in the following areas:
(a)
Laundries.
(b) Maintenance shops,
including woodworking and painting areas.
(c) Rooms or spaces used for the processing
or use of combustible supplies deemed hazardous by the authority having
jurisdiction.
(d) Rooms or spaces
used for processing or use of hazardous materials or flammable or combustible
liquids in quantities deemed hazardous by recognized standards.
(3) Where automatic extinguishing
is used to meet the requirements of section 12.3.2.1.2(1) or (2), the
protection shall be permitted in accordance with section 9.7.1.2.
12.7.1.3. Deleted.
12.7.6.1. In assembly use areas having
occupant loads greater than 1000, there shall be crowd managers or crowd
manager supervisors at a ratio of 1 crowd manager/supervisor for every 250
occupants unless otherwise permitted by any of the following:
(1) This requirement shall not apply to
assembly use areas being utilized for instructional classroom space.
(2) This requirement shall not apply to
assembly occupancies used exclusively for religious worship with occupant load
not more than 2,000.
(3) The ratio
of trained crowd managers to occupants shall be permitted to be reduced where,
in the opinion of the authority having jurisdiction, the existence of an
approved, supervised automatic sprinkler system and the nature of the event
warrant.
12.7.6.2.
Deleted.
12.7.7.2.
Deleted.
12.7.9.3.1.
Deleted.
12.7.9.3.2.
Deleted.
12.7.9.3.3.
Deleted.
13.2.10.3.
Deleted.
13.2.11.2.
Deleted.
13.3.2.1.2. Rooms or spaces
for the storage, processing, or use of materials specified in section
13.3.2.1.2(1) to (3) shall be protected in accordance with the following:
(1) Separation from the remainder of the
building by fire barriers having a minimum 1-hour fire resistance rating or
protection of such rooms by automatic extinguishing systems as specified in
section
8.7
in the following areas:
(a) Boiler and
furnace rooms, unless otherwise permitted by the following:
(i) The requirement of section
13.3.2.1.2(1)(a) shall not apply to rooms enclosing furnaces, heating and air
handling equipment, or compressor equipment with a total aggregate input rating
less than 200,000 Btu (211 MJ), provided that such rooms are not used for
storage.
(ii) The requirement of
section 13.3.2.1.2(1)(a) shall not apply to attic locations of the rooms
addressed in section 13.3.2.1.2(1)(a)(i), provided that such rooms comply with
the draft stopping requirements of section
8.6.10.
(b) Rooms or spaces larger than
100 square feet (4.6 square meters) and used for the storage of combustible
supplies.
(c) Rooms or spaces used
for the storage of hazardous materials or flammable or combustible liquids in
quantities deemed hazardous by recognized standards.
(2) Separation from the remainder of the
building by fire barriers having a minimum 1-hour fire resistance rating and
protection of such rooms by automatic extinguishing systems as specified in
Section
8.7
in the following areas:
(a)
Laundries.
(b) Maintenance shops,
including woodworking and painting areas.
(c) Rooms or spaces used for processing or
use hazardous materials or flammable or combustible liquids in quantities
deemed hazardous by recognized standards.
(3) Where automatic extinguishing is used to
meet the requirements of section 13.3.2.1.2(1) or (2), the protection shall be
permitted pursuant to section 9.7.1.2.
13.7.1.3. Deleted.
13.7.6.1. In assembly occupancies having
occupant loads greater than 1,000, there shall be crowd managers or crowd
manager supervisors at a ratio of 1 crowd manager/supervisor for every 250
occupants unless otherwise permitted by either of the following:
(1) This requirement shall not apply to
assembly occupancies used exclusively for religious worship with occupant load
not more than 2,000.
(2) The ratio
of trained crowd managers to occupants shall be permitted to be reduced where,
in the opinion of the authority having jurisdiction, the existence of an
approved, supervised automatic sprinkler system and the nature of the event
warrant.
13.7.6.2.
Deleted.
13.7.7.2.
Deleted.
13.7.9.3.1.
Deleted.
13.7.9.3.2.
Deleted.
13.7.9.3.3.
Deleted.
43.1.2.1. The portion or
portions of a building undergoing repair, renovation, modification, or
reconstruction shall comply with both of the following:
(1) Requirements of the applicable existing
occupancy chapters.
(2)
Requirements of the applicable section of this chapter.
43.1.4.5. Deleted.