Rule 9. Section 280.20 is amended to read as
follows:
Section 280.20. Performance standards for new UST
systems. In order to prevent releases due to structural failure, corrosion, or
spills and overfills for as long as the UST system is used to store regulated
substances, all owners and operators of new UST systems shall meet the
following requirements. In addition, except for suction piping that meets the
requirements of subparagraphs 280.41(b)(1)(ii)(A) to (E), tanks and piping must
be secondarily contained and use interstitial monitoring in accordance with
subsection 280.43(g) of these rules. Secondary containment must be able to
contain regulated substances leaked from the primary containment until they are
detected and removed and prevent the release of regulated substances to the
environment at any time during the operational life of the UST system. For
cases where the piping meets the definition of "replaced" in section 280.12,
the entire piping run must be secondarily contained.
(a) Tanks. Each tank must meet the definition
of secondary containment as defined in section 280.12 and must be properly
designed and constructed. Any portion of a tank that is underground and that
routinely contains product must be protected from corrosion by 1 of the
following:
(1) The tank must be constructed
of fiberglass-reinforced plastic
(2) The tank must be constructed of steel and
be cathodically protected by all of the following:
(i) The tank must be coated with a suitable
dielectric material.
(ii)
Factory-installed or field-installed cathodic protection systems must be
designed by a corrosion expert.
(iii) Impressed current systems must be
designed to allow a determination of current operating status as required in
subsection 280.31(c).
(iv) Cathodic
protection systems must be operated and maintained in accordance with section
280.31 or according to procedures acceptable to the department.
(3) The tank must be constructed
of a steel-fiberglass-reinforced-plastic composite. The fiberglass-reinforced
plastic must be a minimum of 100 mils thick.
(4) The tank is constructed of metal without
additional corrosion protection measures provided that both of the following
requirements are met:
(i) The tank is
installed at a site that is determined by a corrosion expert not to be
corrosive enough to cause it to have a release due to corrosion during its
operating life.
(ii) Owners and
operators maintain records that demonstrate compliance with the requirements of
paragraph (a)(4)(i) of this section for the remaining life of the
tank.
(5) The department
shall determine that the tank construction and corrosion protection have been
designed to prevent the release or threatened release of any stored regulated
substance in a manner that is at least as protective of human health and the
environment as the protections specified in subdivisions(1) to (3) of this
subsection.
(b) Piping.
All piping in contact with the ground shall be equipped with secondary
containment as defined in section 280.12. Any piping that routinely contains
regulated substances and is in contact with the ground must be properly
designed, constructed, and protected from corrosion in compliance with 1 of the
following provisions:
(1) The piping must be
constructed of fiberglass-reinforced plastic.
(2) The piping must be constructed of metal
and be cathodically protected in the following manner:
(i) The piping must be coated with a suitable
dielectric material.
(ii)
Field-installed cathodic protection systems must be designed by a corrosion
expert.
(iii) Impressed current
systems must be designed to allow a determination of current operating status
as required in subsection 280.31(c).
(iv) Cathodic protection systems must be
operated and maintained in accordance with the provisions of section 280.31 or
procedures acceptable to the department.
(v) Metallic secondary containment
underground piping systems must have corrosion protection as specified in
paragraphs (2)(i) to (iv) of this subdivision.
(3) The piping is constructed of metal
without additional corrosion protection measures provided that both of the
following requirements are met:
(i) The
piping is installed at a site that is determined by a corrosion expert to not
be corrosive enough to cause it to have a release due to corrosion during its
operating life.
(ii) Owners and
operators maintain records that demonstrate compliance with the requirements of
paragraph (b)(3)(i) of this section for the remaining life of the
piping.
(4) The
department shall determine that the piping construction and corrosion
protection have been designed to prevent the release or threatened release of
any stored regulated substance in a manner that is at least as protective of
human health and the environment as the protections specified in subdivisions
(1) and (2) of this subsection.
(c) The following provisions apply to spill
and overfill prevention equipment:
(1) Except
as provided in subdivisions (2) and (3) of this subsection, to prevent spilling
and overfilling associated with product transfer to the UST system, owners and
operators shall use both of the following spill and overfill prevention
equipment:
(i) Spill prevention equipment
that will prevent the release of product to the environment when the transfer
hose is detached from the fill pipe, for example, a spill catchment
basin.
(ii) Overfill prevention
equipment that does 1 of the following:
(A)
Automatically shut off flow into the tank when the tank is not more than 95%
full.
(B) Alert the transfer
operator when the tank is not more than 90% full by restricting the flow into
the tank or by triggering a high-level alarm. For suction pump systems, a
pressure regulator valve or other suitable device must be installed in the
suction piping if the flow restrictor causes a pressure buildup in the tank
when activated.
(C) Restrict the
flow from the delivery truck into the tank 30 minutes before overfill, and
sound an audible alarm 1 minute before overfill, or automatically shut off the
flow into the tank not less than 30 seconds before overfill.
(2) Owners and
operators are not required to use the spill and overfill prevention equipment
specified in subdivision (1) of this subsection if alternative equipment is
used that is determined by the department to be at least as protective of human
health and the environment as the equipment specified in paragraphs (1)(i) or
(1)(ii) of this subsection or the UST system is filled by transfers of no more
than 25 gallons at 1 time.
(3) Flow
restrictors used in vent lines may not be used to comply with paragraph
(c)(1)(ii) of this section when overfill prevention is installed or
replaced.
(4) Spill and overfill
prevention equipment shall be periodically tested or inspected in accordance
with section 280.35 or as otherwise allowed under section 280.10(f).
(d) All tanks and piping must be
properly designed, constructed, installed, operated, and maintained in
accordance with
R 29.5601 to
R 29.5917. All of the following
provisions shall also apply:
(1) Except at an
active UST system location installed on or before January 3, 1991, a person
shall not install an UST system unless the UST system is more than the
following distances from the following items:
(i) All UST system installations must also be
in compliance with section 12701 of part 127 of 1978 PA 368, MCL 333.12701, and
rules promulgated under 1978 PA 368.
(ii) Section 1001 of 1976 PA 399, MCL
325.1001 to 325.1023, and rules promulgated under 1976 PA 399.
(e) Certification of
installation. All owners and operators shall ensure that 1 or more of the
following methods of certification, testing, or inspection are used to
demonstrate compliance with subsection(d) of this section by providing a
certification of compliance on the UST registration form in accordance with
section 280.22:
(1) The installer has been
certified by the tank and piping manufacturer or the tank liner has been
certified by the tank lining manufacturer.
(2) The installer has been certified or
licensed by the department.
(3) The
installation has been inspected and certified by a registered professional
engineer who has education and experience in UST system installation.
(4) The installation has been inspected and
approved by the implementing agency.
(5) All work listed in the manufacturers
installation checklists has been completed.
(6) The owner and operator have complied with
another method for ensuring compliance with the provisions of subsection (d) of
this section that is determined by the department to be at least as protective
of human health and the environment as the protections specified in subsection
(d) of this section.
(f)
Dispenser systems. Each UST system must be equipped with under-dispenser
containment for any new dispenser system installed.
(1) A dispenser system is considered new when
both the dispenser and all of the equipment needed to connect the dispenser to
the UST system are installed at an underground storage tank facility. The
equipment necessary to connect the dispenser to the UST system includes check
valves, shear valves, unburied risers, flexible connectors, or other
transitional components that are underneath the dispenser and connect the
dispenser to the underground piping.
(2) Under-dispenser containment must be
liquid-tight on its sides, bottom, and at any penetrations. Under-dispenser
containment must allow for visual inspection and access to the components in
the containment system or be periodically monitored for leaks from the
dispenser system.