Mich. Admin. Code R. 29.2115 - Operations and maintenance of corrosion protection
Rule 15. Section 280.31 is amended to read as follows:
Section 280.31. All owners and operators of steel UST systems with corrosion protection shall comply with the following requirements to ensure that releases due to corrosion are prevented for as long as the UST system is used to store regulated substances:
(a) All corrosion protection systems are
operated and maintained to continuously provide corrosion protection to the
metal components of that portion of the tank and piping that routinely contain
regulated substances and are in contact with the ground.
(b) All UST systems equipped with cathodic
protection systems are inspected for proper operation by a qualified cathodic
protection tester in accordance with the following requirements:
(1) Frequency. All cathodic protection
systems shall be tested upon completion of underground piping and tank
installation and backfilling, but before placement of any permanent or hard
surface over the UST system. Testing must be done within 6 months of
installation regardless of the surface over the UST system. Testing must also
be conducted every 3 years after the initial testing.
(2) Inspection criteria. The corrosion
engineer who designs the system shall specify the criteria that are used to
determine that cathodic protection is performing adequately. If the corrosion
engineer does not specify criteria, then the criteria must be as specified in
NACE international standard practice SP0285-2011.
(c) UST systems with impressed current
cathodic protection systems shall also be inspected every 60 days to ensure the
equipment is running properly.
(d)
For UST systems using cathodic protection, records of the operation of the
cathodic protection shall be maintained (in accordance with section 280.34) to
demonstrate compliance with the performance standards in this section. These
records must provide both of the following:
(1) The results of the last 3 inspections
required in paragraph (c) of this section.
(2) The results of testing from the last 2
inspections required in paragraph (b) of this section.
(e) For galvanic anode systems equipped with
an approved buried copper-copper sulfate reference electrode that can be read
at a surface test station, the inspection may be made using a test measurement
device designed for tank O/O not meeting the cathodic protection tester
definition. The O/O shall be trained in the testing procedure and shall be
familiar with the testing specifications of the galvanic anode system. Tests
shall be made in accordance with the requirements of subsection (b) of this
section.
(f) Cathodic protection
testing is not required for the following:
(1)
A composite tank which meets the requirements of subsection 280.20(a)(3) and
that is equipped with galvanic anodes installed by the tank manufacturer. The
tank shall be installed and tested in accordance with section
280.20(d).
(2) A 360-degree
double-wall steel tank equipped with galvanic anodes. Interstitial monitoring
of the tank must be conducted in accordance with subsection
280.43(g).
(g) Another
method determined by the department to be equally
protective.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.