Mich. Admin. Code R. 29.5664 - Location of loading and unloading facilities
Rule 664. Sections 28.4.2.1 and 28.4.2.2 are added to the FL/CL code as follows:
28.4.2.1 A fire protected tank or a tank in a
vault is exempt from compliance with the separation distance requirements for
the loading and unloading risers.
28.4.2.2 A tank which has a capacity of 3,000
gallons (11,340 liters) or less which is located 10 feet (3 meters) from any
building, and which is provided with spill and audible overfill protection or
other means acceptable to the bureau based on the best interests of public
health, safety, and welfare and the environment, is exempt from compliance with
the separation distance requirements for loading and unloading
risers.