Mich. Admin. Code R. 325.45277 - Surgical service; examination room; operating or procedure room
Rule 277. A facility that provides surgical services shall meet all the following requirements:
(a) The facility must have enough examination
rooms to meet the volume of work to be accomplished. Each single-patient
examination room must have a minimum clear floor area of 120 square feet and
must provide a minimum 3-foot clearance at each side and the foot of the
examination table. In freestanding surgical outpatient facilities, the room
size may be reduced to 100 square feet and must provide a minimum 3-foot
clearance at each side and at the foot of the examination table.
(b) An examination room must have a handwash
lavatory within the room, which must be equipped with a gooseneck inlet and
wrist, knee, or foot controls.
(c) A
change area must be provided for patients, and provision must be made for the
safe storage of their personal effects.
(d) The facility must have enough operating
or procedure rooms to meet the volume of work to be accomplished and they must
comply with both of the following:
(i) Each
operating room must have a minimum clear floor area of 400 square feet, with a
minimum clear dimension of 20 feet, exclusive of fixed or wall mounted cabinets
and built-in shelves. In freestanding surgical outpatient facilities, where the
surgical procedures are restricted to eye, endoscopy, and other similar minor
procedures, the room size may be reduced to 270 square feet.
(ii) One scrub sink with a gooseneck outlet
must be provided near the entrance to each operating room. A scrub sink with
two positions may be shared between two adjacent operating rooms, provided that
it is located near the entrances to both rooms.
(e) Each procedure room must have a minimum
clear floor area of 160 square feet with a minimum dimension of 12 feet,
exclusive of fixed or wall mounted cabinets and built-in shelves.
(f) A supply of oxygen and appropriate masks
or other means of administration must be available in each room.
(g) Single-use soap, scrub brushes, and
towels must be utilized in patient care areas.
(h) The operating or procedure room must
contain suitable equipment necessary for the types of procedures to be
performed.
(i) Operating rooms and
procedure rooms must be cleaned and disinfected between cases and terminally
cleaned daily in accordance with the facilitys policy and
procedure.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.