Mich. Admin. Code R. 325.45321 - Nurse call system; equipment; telephone
Rule 321.
TABLE 2
Location of Nurse Call Devices
Key: * Required
[] Optional, but must be justified
|
Area Designation |
Patient Station |
Patient Bath Station |
Emergency Signal Station |
Code Call Station |
Nurse Master Station |
Duty Station |
Notes |
|
Nursing Units |
|||||||
|
Inpatient Bed Location |
* |
* |
[] |
||||
|
Patient Water Closets, Showers, and Baths |
* |
||||||
|
Nurse Control Station |
* |
||||||
|
Clean Workroom |
* |
||||||
|
Clean Supply Room |
[] |
||||||
|
Soiled Workroom |
* |
||||||
|
Soiled Holding Room |
[] |
||||||
|
Medication Preparation Room |
* |
||||||
|
Examination or Treatment Room |
[] |
* |
* |
||||
|
Nurse Lounge |
* |
||||||
|
Clean Linen Storage |
[] |
||||||
|
Nourishment Station |
[] |
||||||
|
Equipment Storage Room |
[] |
||||||
|
Multi-Purpose Room |
[] |
||||||
|
Other Clinical Areas |
|||||||
|
Operating or Delivery Rooms |
* |
[] |
|||||
|
Procedure Rooms |
* |
[] |
|||||
|
Labor, Delivery, Recovery, Post-Partum Rooms |
* |
* |
* |
||||
|
Recovery Phase 1 |
[] |
* |
* |
[] |
|||
|
Recovery Phase 2 |
* |
* |
[] |
[] |
|||
|
Emergency Exam, Treatment and Triage Areas |
* |
* |
* |
[] |
1,2,4 |
||
|
Patient Preparation and Holding Areas |
* |
* |
[] |
[] |
1,2 |
||
|
Critical Care Bed Locations, including NICU |
* |
* |
* |
[] |
1,2,3,4 |
||
|
Newborn and Special Care Nurseries |
* |
[] |
|||||
|
Cardiac Catheterization, Interventional and Radiological Areas Angiography |
[] |
* |
* |
[] |
|||
|
MRI, CT, Stress Testing Areas |
[] |
* |
* |
2,4 |
|||
|
Outpatient Examination Areas |
[] |
[] |
|||||
|
Outpatient Waiting and Changing Areas |
[] |
2 |
|||||
|
Psychiatric Seclusion, Ante, and Exam Rooms |
* |
[] |
|||||
|
Outpatient Toilet Rooms, Showers, Baths |
[] |
2 |
|||||
|
Psychiatric Patient 2 Room |
[] |
2 |
|||||
|
Notes: |
|||||||
|
1. One device may accommodate both patient station and emergency staff assistance station functionality. |
|||||||
|
2. Must activate a visible signal in the corridor at the patients door, at the nurse control station, and all duty stations. |
|||||||
|
3. Provide 2-way voice communication with nurse control station. |
|||||||
|
4. One device may accommodate both emergency staff assistance and code call station functionality. |
|||||||
|
5. Patient station not required in NICU. |
|||||||
Notes