Mich. Admin. Code R. 339.5209 - Non-boiler external piping; power boilers; adoption and amendment of standards

Rule 209.

(1) An owner of a boiler shall ensure that the installation of piping not covered by the ASME boiler and pressure vessel code, section I, 2019 edition, is installed as prescribed by the ASME code for pressure piping, B31.1, 2018 edition.
(2) The owner of a chemical plant or petroleum refinery shall comply with subrule (1) of this rule or ensure the installation is installed as prescribed by ASME code for chemical plants and petroleum refineries, B31.3, 2019 edition.
(3) A licensee under this rule is not required to possess an ASME code symbol stamp, but must hold a valid installers license.
(4) The owner shall ensure that the installation of all of the following piping meets the requirements under subrule (1) of this rule:
(a) Blowoff piping beyond the second valve out to the safe point of discharge.
(b) Steam piping out to the load.
(c) Feed-water piping from the pump.
(d) Condensate piping.