Mich. Admin. Code R. 339.5234 - Steam kettles

Rule 234.

(1) A fired or electrically heated steam kettle, irrespective of size, that has piped feed connections must comply with these rules.
(2) A fired or electrically heated kettle, irrespective of size without feed piping connections, must comply with these rules. Instead of an installation permit, an owner or user shall report the installation to the chief inspector before the unit is operated. The chief inspector shall assign a deputy inspector to visit the installation location to inspect the kettle to determine its safety for operations. A kettle that is operated at or below 15 psi must be inspected biennially. A kettle that is operated at more than 15 psi must be inspected annually.
(3) Steam kettles manufactured to ASME section VIII division-1 2019 must have the minimum appurtenances and controls that are required in mandatory appendix 19.

Notes

Mich. Admin. Code R. 339.5234
2023 MR 8, Eff. 5/3/2023