Mich. Admin. Code R. 339.5237 - Platforms

Rule 237.

(1) A platform must be installed at 1 end of all drums of a water tube boiler that are more than 4 feet above the floor or walkway to permit safe access to the interior of the drums for cleanout and inspection.
(2) An inspector shall notify the owner or user who is required to conform to this rule and give written notice of a violation to the owner or user that the installation of the required stairway, runaway, platform, or ladder is to be made. The owner or user is allowed 1 year from the date of the violation to complete the work.
(3) A licensee may request a deviation from the requirements of this rule by submitting drawings to the chief inspector for review and approval before installation of the boiler. The chief inspector shall notify the licensee of the approval or denial of the request.

Notes

Mich. Admin. Code R. 339.5237
2023 MR 8, Eff. 5/3/2023