Mich. Admin. Code R. 400.10619 - Fire extinguishers
Rule 619.
(1) All
required fire extinguishers in residential group home facilities shall be
subjected to a maintenance check at least once a year.
Each fire extinguisher shall have a tag or label attached that indicates the month and year maintenance was performed and that identifies the person or company that performs the service.
(2) All required extinguishers shall be
recharged after use.
(3) A minimum
of 1 approved fire extinguisher shall be provided on each floor.
(4) All fire extinguishers shall be not less
than 4 inches off the floor and the top of the extinguisher shall be not more
than 5 feet off the floor in a special cabinet or on a wall rack which is
easily accessible at all times, unless programmatically contraindicated. Where
programmatically contraindicated, the required extinguishers may be kept behind
locked doors if all staff carry keys to the doors.
(5) In new, remodeled, or converted
facilities, a fire extinguisher shall be at least a type 2-A-10BC.
(6) In existing facilities, previously
approved fire extinguishers other than type 2-A-10BC will continue to be
approved if they are located in the area for which approved.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.