Mich. Admin. Code R. 400.11217 - Heating
Rule 217.
(1)
Heating shall be by a central heating plant, a permanently installed electrical
system, or a sealed combustion unit or units mounted on an outside
wall.
(2) A central heating plant
shall be installed in a 1-hour-fire-resistant enclosure that includes a
B-labeled fire door and frame assembly in any interior opening. Combustible
ducts shall not be used inside of, or penetrate a required fire-rated
enclosure. Air for proper combustion shall be drawn directly from the outside
of the building by a permanently open louver, and approved mechanically
operated automatic louver or noncombustible duct. A fuel-fired central heating
plant requires fire damper installations where ducts penetrate a 1-hour fire
rated enclosure except where the heating plant complies with either subrule
(6), (7), or (8) of this rule.
(3) A
permanently installed electrical system shall be either baseboard or panel. It
shall be listed by a nationally recognized independent testing laboratory and
installed according to the manufacturer's specifications.
(4) In new construction, additions,
conversions, or remodeling, roof-mounted, fuel-fired heating units shall be
separated from any building that is used for camper sleeping by at least
1-hour-fire-resistive construction. In all camper-occupied buildings, whether
used for camper sleeping or not, roof-mounted fuel-fired heating units shall be
installed in accordance with the manufacturer's specifications utilizing
industry-recognized methods and materials.
(5) A sealed combustion unit shall be
approved by a nationally recognized testing laboratory, mounted on an outside
wall, properly vented, and installed according to the manufacturer's
specifications.
(6) In new
construction and conversions where buildings are used for sleeping and where an
electrically powered smoke detection system is not required, there shall be a
duct smoke detector installed ahead of the fresh air intake in the return air
duct of the system so that upon smoke detector activation, the fan to the
heating unit will shut down.
(7)
Buildings used for sleeping and requiring an electrically powered fire
detection system shall have the system connected to the furnace so that
activation of the fire detection system will shut down the fan. This is not
required if either of the following provisions is complied with:
(a) Approved fire dampers are installed at
all duct penetrations in the heat plant enclosure.
(b) The heating system has a duct smoke
detector installed ahead of the fresh air intake on the return air portion of
the system, as permitted in subrule (6) of this rule, so that activation of the
detector will shut down the fan and sound the building fire alarm.
(8) Fire dampers are not required
to be installed in the heating plant room enclosure of a building that is not
used for sleeping.
(9) A
flame-producing water heater shall be installed in either the same enclosure as
the heating plant or in a separate enclosure that affords the same
protection.
(10) In a building that
is not used for sleeping additional protection is not required for the
fuel-fired heating plant or water heater if all of the following are met:
(a) The heating plant and/or water heater is
located in a basement that is not used by campers.
(b) There is approved floor separation
consisting of minimum of standard partition construction between the basement
and the remainder of the building.
(c) The basement is not used for the storage
of any combustibles without a 1-hour fire resistive separation between the
storage and the heating plant. Any doorways in the separation wall(s) shall be
protected with "B" labeled fire door/frame assemblies, including self-closing
devices and positive latching hardware.
(11) A portable heating unit shall not be
used in a camper-occupied building.
(12) A solid fuel-burning space heater shall
not be installed in a building that is used for sleeping. A solid fuel-burning
heating appliance, that is approved by an independent nationally recognized
testing laboratory and that is installed according to the manufacturer's
specifications, may be installed in a non-sleeping occupancy. A chimney shall
be inspected and a proper and thorough cleaning shall be performed at least
once every 2 months during the heating season. Prefabricated chimneys may be
installed in accordance with their listings. A masonry chimney shall be
provided with an approved fire clay flue liner.
(13) A central, solid fuel-burning heating
plant may be approved if it is enclosed by a minimum of 1-hour-fire-resistant
construction and if it is installed according to test and manufacturer's
specifications. Due to the possibility of ambient heat buildup in small
enclosures, strict safe engineering practices shall be followed to allow for
the proper dispersion of excessive heat and the intake of adequate combustion
air.
(14) A boiler shall be
inspected and certified as required by the boiler division of the bureau of
construction codes of the department of energy, labor, and economic
growth.
(15) A masonry fireplace may
be used if it is provided with an approved screen or glass device to prevent
the spread of fire and embers and if the chimney is provided with an approved
fire clay flue liner or consists of a properly installed U.L. listed
prefabricated metal chimney. The chimney shall be visually inspected every
other month while in use and cleaned as needed but no less than once every 12
months. A fireplace shall have a noncombustible hearth that extends a minimum
of 20 inches out from the front, and 12 inches beyond each side of the
fireplace opening and a noncombustible face that extends not less than 12
inches above, and 12 inches on each side of the fireplace opening.
(16) In new construction, additions,
conversions or remodeling, a gas-log fireplace may be used if the fireplace is
provided with an approved screen or glass device, it vents products of
combustion directly to the outside, and it is installed and maintained in
strict accordance with the manufacturer's specifications. The installation
shall be approved by the mechanical inspector having jurisdiction.
(17) In new construction, additions,
conversions or remodeling, fireplaces shall not be installed in a camper
sleeping building unless there is a 1-hour fire resistive separation, including
45-minute fire-rated door/frame assemblies, between the fireplace use area and
the camper sleeping area and with each area having proper independent exiting.
In existing licensed camp buildings that are used for sleeping, fireplaces may
only be used if they meet the requirements of this subrule or are properly
fitted with a sealed combustion gas-log insert that requires tools to access
any open flame. The flames shall be kept inaccessible to campers, and the
insert must comply with subrule (5) of this rule for location and
installation.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.