Mich. Admin. Code R. 400.11219 - Combustible storage; other hazardous areas
Rule 219.
(1) New
construction, additions, conversions, or remodeling, rooms that are used for
the storage of combustible materials, or hazardous materials, and are larger
than 100 square feet in area, shall have walls and ceilings that are
constructed of 1-hour fire resistive construction. Interior doorways to such
storage rooms shall be protected with B-labeled fire doors set in labeled frame
assemblies complete with approved self-closing devices and positive
self-latching hardware. Where such rooms are 100 square feet or smaller, they
shall have walls and ceilings that are constructed of at least 5/8-inch drywall
and any interior door openings to such rooms shall be protected with a minimum
of a 1 3/4-inch solid wood core door or equivalent that has a self-closing
device and positive self-latching hardware.
(2) In existing buildings approved for camper
use, storage rooms that were approved before these rules take effect shall
continue to be approved with regard to enclosure until the portion of the
facility containing the storage area is remodeled or the facility is converted.
At a minimum, these storage rooms shall have approved noncombustible walls and
ceilings and any door openings shall be protected with minimum of 1 --inch,
solid core wood doors equipped with approved self-closing devices and positive
self-latching hardware. This shall not preclude requirements relative to
maintaining doors and other safety features in proper working order.
(3) Combustible storage shall not be allowed
in a heating plant room.
(4) In new
construction, additions, conversions or remodeling, combustible storage is
allowed beneath a stairway. If the storage area is enclosed in 1-hour fire
resistive construction including a "B" labeled fire door/frame assembly with an
approved self-closing device and positive latching hardware.
(5) In new construction, additions,
conversions, or remodeling, other hazardous areas in camper-occupied buildings,
including areas housing commercial-style kitchens, commercial-style laundries,
motor vehicle garages, incinerators, or other similar hazards, shall be
enclosed with 1-hour fire resistive construction. Any interior door openings
shall be protected with B-labeled fire doors, set in labeled frame assemblies
and equipped with approved self-closing devices and positive latching hardware.
Where commercial cooking equipment is properly protected by an approved
automatic kitchen hood suppression system, the kitchen shall be exempt from the
enclosure requirements of this rule.