Mich. Admin. Code R. 400.18622 - Hot water heaters and storage tanks
Rule 622.
(1) A hot
water heater, other than an electrically heated heater or a booster heater for
a dishwasher or for laundry purposes, shall be installed in the heating plant
or in an enclosure of like fire-resistant construction and shall not be used
for the storage of any combustible material.
(2) A hot water storage tank shall be
equipped with a safety device that prevents temperatures of more than 210
degrees Fahrenheit and pressures in excess of the maximum working pressure for
which the tank is designed from being reached. Any of the following are
acceptable safety devices:
(a) An acceptable
pressure relief valve that is combined with an energy cutoff approved by
underwriters laboratories, incorporated, or the American gas
association.
(b) An acceptable
pressure relief valve and an acceptable temperature relief valve of the
spillage type.
(c) An acceptable
combined temperature-pressure relief valve of the spillage type.