Mich. Admin. Code R. 400.8530 - Hazard Areas
Rule 530.
(1)
Hazard areas must be separated from the parts of the building used as a center
in the following manner:
(a) In centers
licensed before June 4, 1980, areas used for the storage of combustibles and
other hazard areas are approved if they are enclosed with a minimum 3/4-hour
fire resistive construction and doorways to the areas are protected with a
minimum 13/4-inch flush solid core wood or 20-minute labeled fire-rated doors
equipped with approved self-closing devices and positive latching
hardware.
(b) In centers licensed
between June 4, 1980 and July 1, 2000, areas used for the storage of
combustibles and other hazards are approved if they are enclosed by 1 of the
following:
(i) If the area used for the
storage of combustibles exceeds 100 square feet, by construction having a
minimum 1-hour fire resistance rating, openings in the separation must be
protected with a minimum of 45-minute rated fire door assembly, including an
approved self-closing device and positive latching hardware. "B" labeled doors
are acceptable.
(ii) If the area
used for the storage of combustibles does not exceed 100 square feet, by
construction having a minimum 3/4-hour fire resistance rating, all door
openings must be protected by minimum 13/4-inch flush solid core wood doors or
20-minute labeled fire-rated doors hung in substantial frames and equipped with
approved self-closing devices and positive latching
hardware.
(c) In centers
licensed after July 1, 2000, areas used for the storage of combustibles and
other hazards are approved if they are enclosed by 1 of the following:
(i) If the area used for the storage of
combustibles exceeds 100 square feet, by construction having a minimum 1-hour
fire resistance rating, openings in the separation must be protected with a
minimum of 45 minute-rated fire door assembly, including an approved
self-closing device and positive latching hardware. "B" labeled doors are
acceptable.
(ii) If the area used
for the storage of combustibles does not exceed 100 square feet, by
construction having a minimum 1-hour fire resistance rating. All door openings
must be protected by minimum 13/4 inch flush solid core wood doors or 20-minute
labeled fire-rated doors in substantial frames and equipped with approved
self-closing devices and positive latching hardware.
(iii) If the area is used for the storage of
combustibles, including basements and areas adjacent to the licensed area, a
room must be protected according to subrule (1)(c)(i) or (ii) of this
rule.
(2) If a
kitchen with fuel-fired appliance cooking equipment exposes a required means of
egress or child use area, it must be separated from the remainder of the
building with minimum 1-hour fire resistive construction, including a minimum
of 45-minute rated fire door assemblies in all common openings. Kitchens having
fuel-fired appliance cooking equipment protected by an approved automatic
kitchen hood suppression system are exempt from this requirement. "B" labeled
doors are acceptable.
(3) The use
of an incinerator is prohibited.
(4) Heating must be by a central heating
plant or an approved permanently installed electrical heating system. If
heating is provided by a central heating plant and located on the same floor
that is used for child occupancy or adjacent to the licensed area such as the
basement or attic, it must be installed in an enclosure providing not less than
a 1-hour fire-resistive separation, including a minimum of 45-minute rated fire
door assembly equipped with an approved self-closing device and positive
latching hardware in any interior door opening.
(5) In centers licensed before December 7,
2006, a properly installed heating plant located in a basement that is not used
for child occupancy does not require additional protection if there is a
qualified fire separation and with not less than a 13/4-inch flush solid core
wood doors or 20-minute labeled fire-rated doors hung in a substantial frame
and equipped with an approved self-closing device and positive latching
hardware in all stairway openings.
(6) Any fuel-fired appliance must be located
according to subrule (4) or (5) of this rule, as applicable.
(7) If electric heating is used, it must be
Underwriters' Laboratories, Inc. (UL) listed, permanent, fixed-type electrical
heating such as recognized panel or baseboard fixed-type. Electric heating that
complies with this requirement may be installed in any location.
(8) Auxiliary heating units, such as portable
combustion or electrical types, are prohibited.
(9) The center shall not store flammable
materials, including fuels, pressurized cans, cleaning fluids and supplies,
polishes, and matches, in heat plant enclosures. These items may be stored
outside of child use areas in metal cabinets or storage facilities accessible
only to authorized staff.
(10) The
center shall not store combustible materials within the central heating plant
or fuel-fired water heater rooms or in basements containing fuel-fired heating
equipment, without a proper fire separation.
(11) The center shall not allow flammable
gases, gasoline, or gasoline-powered equipment in the part of a building that
is used as a center or in other parts of the building from which there is a
door, window, or other opening into the center, unless that part of the
building is separated from the remainder of the building by minimum 2-hour fire
resistive construction.
(12) If a
fuel-fired laundry equipment is installed, the equipment must be enclosed to
provide a 1-hour resistance to fire, including a minimum of 45-minute rated
fire door assembly in an interior door opening that would expose the center.
"B" labeled doors are acceptable.
(13) Dryer vents must be metal or
Underwriters' Laboratories, Inc (UL) listed flexible transition duct and vented
completely to the exterior.
(14)
The department does not require fire dampers in 3/4-hour and 1-hour
fire-resistive enclosures.
(15) All
appliances and equipment in the center must be installed and maintained in
accordance with their manufacturer's specifications.
(16) Centers shall be maintained free of all
conditions that constitute fire safety hazards.
(17) When oxygen is needed for a child in
care, all of the following must apply:
(a) The
center shall not store more than a day's worth of oxygen on the premises and
only when the child is in attendance.
(b) Tanks that are not in use must be secured
from tipping over and labeled as full or empty.
(c) Signs stating "Oxygen in Use" must be
posted at every entrance of the building.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
Rule 530.
(1) Hazard areas shall be separated from the parts of the building used as a center in the following manner:
(a) In centers licensed before June 4, 1980, areas used for the storage of combustibles and other hazard areas will continue to be approved if they are enclosed with a minimum 3/4-hour fire resistive construction and doorways to the areas are protected with a minimum 13/4-inch flush solid core wood or 20-minute labeled fire-rated doors equipped with approved self-closing devices and positive latching hardware.
(b) In centers licensed between June 4, 1980 and July 1, 2000, areas used for the storage of combustibles and other hazards will continue to be approved if they are enclosed by 1 of the following:
(i) Where the area used for the storage of combustibles exceeds 100 square feet, by construction having a minimum 1-hour fire resistance rating, openings in the separation shall be protected with a minimum of 45-minute rated fire door and frame assembly, including an approved self-closing device and positive latching hardware. "B" labeled doors are acceptable.
(ii) Where the area used for the storage of combustibles does not exceed 100 square feet, by construction having a minimum 3/4-hour fire resistance rating, all door openings shall be protected by minimum 13/4-inch flush solid core wood doors or 20-minute labeled fire-rated doors hung in substantial frames and equipped with approved self-closing devices and positive latching hardware.
(c) In centers licensed after July 1, 2000, areas used for the storage of combustibles and other hazards will continue to be approved if they are enclosed by 1 of the following:
(i) Where the area used for the storage of combustibles exceeds 100 square feet, by construction having a minimum 1-hour fire resistance rating, openings in the separation shall be protected with a minimum of 45 minute-rated fire door and frame assembly, including an approved self-closing device and positive latching hardware. "B" labeled doors are acceptable.
(ii) Where the area used for the storage of combustibles does not exceed 100 square feet, by construction having a minimum 1-hour fire resistance rating. All door openings shall be protected by minimum 13/4 inch flush solid core wood doors or 20-minute labeled fire-rated doors in substantial frames and equipped with approved self-closing devices and positive latching hardware.
(2) Where a kitchen with commercial cooking equipment exposes a required means of egress or child use area, it shall be separated from the remainder of the building with minimum 1-hour fire resistive construction, including a minimum of 45-minute rated fire door and frame assemblies in all common openings. Kitchens having commercial cooking equipment protected by an approved automatic kitchen hood suppression system are exempt from this requirement. "B" labeled doors are acceptable.
(3) The use of an incinerator is prohibited.
(4) Heating shall be by a central heating plant or an approved permanently installed electrical heating system . If heating is provided by a central heating plant and located on the same floor that is used for child occupancy, it shall be installed in an enclosure providing not less than a 1-hour fire-resistive separation, including a minimum of 45-minute rated fire door and frame assembly equipped with an approved self-closing device and positive latching hardware in any interior door opening. Door openings for heat plant enclosures not located on the same floor that is used for child occupancy may have 13/4-inch flush solid wood core doors or 20-minute labeled fire-rated doors having positive latching hardware and an approved self-closing device. Air for proper combustion, a minimum of 1 square inch per 4,000 BTUs input, shall be provided directly from the outside through a permanently opened louver or metal duct. "B" labeled doors are acceptable.
(5) In centers licensed before December 7, 2006, a properly installed heating plant located in a basement that is not used for child occupancy does not require additional protection where there is a qualified fire separation and with at least a 13/4-inch flush solid core wood doors or 20-minute labeled fire-rated doors hung in a substantial frame and equipped with an approved self-closing device and positive latching hardware in all stairway openings.
(6) Any fuel-fired water heater or other similar equipment shall be located according to subrule (4) or (5) of this rule, as applicable.
(7) Where electric heating is used, it shall be Underwriters Laboratories, Inc. (UL) listed , permanent, fixed-type electrical heating such as recognized panel or baseboard fixed-type. Electric heating that complies with this requirement may be installed in any location .
(8) Auxiliary heating units, such as portable combustion or electrical types, are prohibited.
(9) The center shall not store flammable materials, including fuels, pressurized cans, cleaning fluids and supplies, polishes, and matches, in heat plant enclosures. These items may be stored outside of child use areas in metal cabinets or storage facilities accessible only to authorized personnel .
(10) The center shall not store combustible materials within the central heating plant or fuel-fired water heater rooms or in basements containing fuel-fired heating equipment, without a proper fire separation.
(11) The center shall not permit flammable gases, gasoline, or gasoline-powered equipment in the part of a building that is used as a center or in other parts of the building from which there is a door, window, or other opening into the center, unless that part of the building is separated from the remainder of the building by minimum 2-hour fire resistive construction.
(12) If commercial-type laundry equipment is installed, then the equipment shall be enclosed to provide a 1-hour resistance to fire, including a minimum of 45-minute rated fire door and frame assembly in an interior door opening that would expose the center. "B" labeled doors are acceptable.
(13) Dryer vents shall be metal and vented completely to the exterior.
(14) The department does not require fire dampers in 3/4-hour and 1-hour fire-resistive enclosures.
(15) All appliances and equipment in the center shall be installed and maintained in accordance with their manufacturers specifications.
(16) Centers shall be kept free of all conditions that constitute fire safety hazards.