Mich. Admin. Code R. 408.10569 - Electrical requirements
Rule 569. The following electrical requirements apply to buildings that utilize working platforms for building maintenance:
(a) General building electrical installations
shall be in compliance with the provisions of General Industry Safety Standard
Part 39 "Design Safety Standards for Electrical Systems," as referenced in
R
408.10509.
(b) Building electrical wiring shall be of
such capacity that when a full load is applied to the equipment power circuit
not more than a 5% drop from building service-vault voltage will occur at any
power circuit outlet that is used by equipment regulated by these
rules.
(c) The equipment power
circuit shall be an independent electrical circuit that remains separate from
all other equipment within or on the building, other than power circuits that
are used for hand tools which will be used in conjunction with the equipment.
If the building has an emergency power system, the equipment power circuit may
also be connected to this system.
(d) The power circuit shall be provided with
a disconnect switch that can be locked in the "off" or "on" position. The
switch shall be located to allow the operators of the equipment access to the
switch.
(e) The disconnect switch
for the power circuit shall be locked in the "on" position when the equipment
is in use.