Mich. Admin. Code R. 408.10647 - Revolving doors
Rule 647.
(1)
A revolving door shall be considered an approved exit door only if all of the
following conditions are satisfied:
(a) The
door shall be installed before the prohibition listed in subrule (2) of this
rule.
(b) The number of revolving
doors used as exit doors shall not be more than the number of swinging doors
used as exit doors within 20 feet thereof.
(c) A revolving door without an adjacent
swinging door may serve as an exit for a street floor elevator lobby if no
stairway or door from other parts of the building discharges through the lobby
and the lobby has no occupancy other than as a means of travel between
elevators and the street.
(d) A
revolving door shall be equipped with means to prevent its rotation at more
than 12 1/2 revolutions per minute.
(e) A revolving door shall not be used at the
foot of stairs from upper floors or at the head of stairs from the basement or
other lower floors.
(f) A revolving
door credited as an exit door shall have a rated capacity of 1/2 unit of exit
width.
(2) A revolving
door that is installed after June 15, 1990, shall not be considered an approved
exit door.