Mich. Admin. Code R. 408.10916 - Gravity, suction, and pressure tanks
Rule 916.
(1) A
gravity or suction water tank shall be maintained at the full water level
designed for fire protection purposes.
(2) The water and air in a pressure water
tank shall be maintained at the designed levels and pressures.
(3) The water in a gravity, suction, or
pressure tank and risers shall be maintained above freezing temperature. Where
a heater is used, the water temperatures shall be not more than 60 degrees
Fahrenheit.
(4) A steel water tank
shall be inspected not less than every 3 years for deterioration and, when
necessary, repairs made.
(5) A
wooden water tank shall be inspected not less than every 2 years for
deterioration and, when necessary, repairs made.