Mich. Admin. Code R. 408.10955 - Inspection
Rule 955.
(1)
A dry chemical extinguishing system shall be inspected by a trained and
authorized employee or outside service:
(a)
Not less than annually to insure operability.
(b) Not less than semiannually to insure the
installed expellant gas containers are at the designed pressure or
weight.
(c) Not less than
semiannually to insure the stored pressure dry chemical container is at the
designed pressure.
(2) A
tag shall be affixed indicating the date of inspection.