Mich. Admin. Code R. 408.11231 - Oxygen manifolding
Rule 1231.
(1)
An oxygen manifolding unit shall be located not less than 20 feet from
combustible materials or separated by a noncombustible barrier, not less than 5
feet high, having a fire-resistance rating of at least 1/2 hour.
(2) An oxygen manifold shall not be located
in acetylene generating rooms.
(3)
Each container and manifold unit shall be labeled to show the name of the gas
contained.
(4) Each manifold shall
be provided with approved pressure regulation devices.