Mich. Admin. Code R. 408.11292 - Stationary acetylene generators
Rule 1292.
(1)
An acetylene generator shall be installed level and in a manner not to place a
strain on the generator or its connections. A generator shall be electrically
grounded.
(2) A generator shall be
located where water will not freeze. Heating shall be by steam, hot water, or
other indirect means. Open flames, fire, or other sources of ignition shall not
be permitted inside a generator house, room, or in any enclosure communicating
with them. Sodium chloride or other corrosive chemicals shall not be used for
protection against freezing.
(3) A
water supply line to an acetylene generator with a noncontinuous connection
shall terminate not less than 2 inches (5.08 centimeters) above the fill
opening so that the water can be observed as it enters the generator. A supply
line with a continuous connection shall be used only when the generator is
provided an open overflow or an automatic water shutoff which will prevent
overfilling the generator.
(4) An
acetylene generator shall discharge only through an open connection into a
vented outdoor receptacle or residue pit.
(5) Each generator shall be provided with a
vent pipe of galvanized iron or steel. The pipe shall be secured to the
building without a trap and shall be installed so that condensation will drain
back to the generator. The pipe shall carry to outside the building and shall
terminate in a hood or bend not less than 12 feet from the ground and 3 feet
(.91 meters) from combustible construction, away from a window or other opening
in a building and any source of ignition, and shall be constructed so that
rain, snow, insects, or birds cannot obstruct the opening. The vent pipes from
several generators shall not be interconnected, but shall lead outside
separately.