Mich. Admin. Code R. 408.13388 - Design requirements for other types of electrical protective equipment
Rule 3388.
Note 1 to subrule (2): These voltages include transient over-voltages, such as switching surges, as well as nominal line voltage. See General Industry Safety Standard Part 86 "Electric Power Generation, Transmission, and Distribution," Appendix B, as referenced in R 408.13301a, for a discussion of transient over-voltages on electric power transmission and distribution systems.
Note 2 to subrule (2): See IEEE 516 "Guide for Maintenance Methods on Energized Power Lines," 2009 edition, as adopted in R 408.13301a, for methods of determining the magnitude of transient over-voltages on an electrical system and for a discussion comparing the ability of insulation equipment to withstand a transient overvoltage based on its ability to withstand alternating current voltage testing.
Note 1 to subrule (3): This rule shall apply to equipment that provides primary insulation of employees from energized parts. It does not apply to equipment used for secondary insulation or equipment used for brush contact only.
Note 2 to subrule (3): For alternating current excitation, this current consists of the following three components:
The conduction current shall be normally negligible. For clean, dry insulating equipment, the leakage current shall be small, and the capacitive current shall predominate.
Note 3 to subrule (3): Plastic guard equipment is considered to conform to the performance requirements of this rule, if it meets, and is used in accordance with ASTM F-712 "Standard Test Methods and Specifications for Electrically Insulating Plastic Guard Equipment for Protection of Workers," 2006 edition with 2011 supplement, as adopted in R 408.13301a.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.