Mich. Admin. Code R. 408.30530 - Requirements for discharge pipe
Rule 530. Section P2803.6.1 of the
P2803.6.1.
Requirements for discharge pipe. Relief valves shall not discharge so as to be
a hazard, a potential cause of damage, or a nuisance.
A relief valve
(a) Shall terminate atmospherically not more
than 4 inches (102 mm) from the floor with an unthreaded end.
(b) Shall not be interconnected .
(c) Valves shall not be connected in the
relief valve discharge pipe.
(d)
Shall be rigid pipe approved for water distribution, with a minimum temperature
rating of 210 degrees Fahrenheit.
(e) Shall have the same nominal inside
diameter as the relief valve outlet and shall drain by gravity flow.
(f) Shall discharge to the floor, or to the
pan serving the water heater or storage tank, or to a waste receptor.
The outlet of a