Mich. Admin. Code R. 408.30534 - Venting
Rule 534. Section P3105.1 is amended and section 3105.4
and figure P3105.4 are added to the
P3105.1. Distance of trap from vent. Each
fixture trap shall have a protecting vent located so that the slope and the
developed length in the fixture drain from the trap weir to the vent fitting
are within the requirements in table P3105.1 of the code .
P3105.4. Vertical leg for waste fixture
drains. A vertical leg (see figure P3105.4) is permitted within a fixture drain
of a waste fixture in accordance with the following criteria:
(1) Minimum trap diameter shall be in
accordance with table P3201.7 of the code .
(2) The diameter of section A shall be equal
to the diameter of the trap.
(3)
The length of section A shall not be less than 8 inches (2032 mm) and in
accordance with table P3105.1 of the code .
(4) The diameter of section B shall be 1 pipe
size larger than the diameter of Section A.
(5) The length of section B shall not be more
than 36 inches (9144 mm).
(6) The
diameter of section C shall be 1 pipe size larger than the diameter of section
B.
(7) The total length of section
A and section C shall not exceed the distance allowed in table P3105.1 of the
code .
(8) Bends shall be the
diameter of the largest connected section.
Click Here To View Image
FIGURE P3105.4
VERTICAL LEG FIXTURE DRAIN SCHEMATIC
Figure N3. Typical liorizontal wet venting.
Click Here To View Image