Mich. Admin. Code R. 408.30535 - Connection
Rule 535. Section P3111.2.2 of the
P3111.2.2.
Connection. The combination waste and vent systems shall be provided with a dry
vent connected to a point within the system or the system shall connect to a
horizontal drain that is vented in accordance with one of the methods specified
in this chapter. Combination waste and vent systems connecting to building
drains receiving only the discharge from a stack or stacks shall be provided
with a dry vent. The vent connecting the combination waste and vent pipe shall
extend vertically not less than 6 inches (152 mm) above the flood level rim of
the highest fixture being vented before offsetting horizontally.