Mich. Admin. Code R. 408.30537 - Separate outdoor electric space conditioning equipment
Rule 537.
Section E3601.6.3, E3601.6.4, and E3608.1.2.1 are added
to the
E3601.6.3. Separate outdoor
electric space conditioning equipment. A service disconnect for separately
metered outdoor electric space conditioning equipment shall be grouped with the
service disconnecting means for the structure or immediately adjacent to the
outdoor meter cabinet. A permanent plaque or directory shall be installed at
each service disconnect location denoting the other services, feeders, and
branch circuits supplying a building or structure and area served by each
service , feeder, and branch circuit. Grounding shall be in accordance with
Sections E3607 and E3608
E3601.6.4.
Electric vehicle charging system service disconnect. A service disconnect for
electric vehicle charging systems shall be grouped with the service
disconnecting means for the structure or immediately adjacent to the outdoor
meter cabinet. A permanent plaque or directory shall be installed at each
service disconnect location identifying the other services, feeders, and branch
circuits supplying a building or structure and area served by each service ,
feeder, and branch circuit. Grounding shall be in accordance with Section E3607
and E3608.
E3604.2.1. Above roofs.
Conductors shall have a vertical clearance of not less than 8 feet (2438 mm)
above the roof surface. The vertical clearance above the roof level shall be
maintained for a distance of not less than 3 feet (914 mm) in all directions
from the edge of the roof. See figure E3604.2.1. [230.24(A)]
Exceptions:
1.
Conductors above a roof surface subject to pedestrian traffic shall have a
vertical clearance from the roof surface in accordance with Section E3604.2.2.
[230.24(A) Exception 1]
2. Where
the roof has a slope of 4 inches (102 mm) in 12 inches (305 mm) or greater and
is not accessible from an operable window, the minimum clearance shall be 3
feet (914 mm). [230.24(A) Exception 2 amended]
3. The minimum clearance above only the
overhanging portion of the roof shall not be less than 18 inches (457 mm) where
not more than 6 feet (1 829 mm) of conductor length passes over 4 feet (1 219
mm) or less of roof surface measured horizontally and such conductors are
terminated at a through-the-roof raceway or approved support. [230.24(A)
Exception 3]
4. The requirement for
maintaining the vertical clearance for a distance of 3 feet (914 mm) from the
edge of the roof shall not apply to the final conductor span where the service
drop is attached to the side of a building . [230.24(A) Exception 4]
5. Where the voltage between conductors does
not exceed 300 and the roof area is guarded or isolated, a reduction in
clearance to 3 feet (914 mm) shall be permitted. [230.24(A) Exception 5]
E3608.1.2.1. Verification of the installation of the concrete encased electrode
specified for in E3608.1.2. The inspection of a concrete incased electrode
meeting the requirements of E3608.1.2 except for the connection of the
grounding electrode conductor to the electrode shall be completed by 1 of the
following:
1. The electrical inspector for
the enforcing agency .
2. The
building inspector for the enforcing agency if all of the following conditions
are met:
a. Both the electrical and building
inspectors for the enforcing agency (s) shall sign a written agreement which
shall remain on file with the enforcing agency that designates authority to the
building inspector for that agency to inspect a concrete encased
electrode.
b. Upon inspection and
verification by the building inspector of a concrete encased electrode, the
building inspector shall provide written documentation to the electrical
inspector that the installation of the concrete encased electrode meets the
requirements set forth in E3608.1.2. Electrode shall be ½" diameter
(13mm) reinforcing bar or larger, a minimum of 20 feet (6 096 mm) long
including usual tie wire connections, and encased in 2 inches (51 mm) of
concrete except for the end of the electrode which shall be in an accessible
location and not subject to deteriorating conditions (i.e. backfill).
c. Verification of approval of the concrete
encased electrode shall be made at the construction site by signature of the
field copy of the building permit noting that the concrete encased electrode
was approved along with the footing inspection or by a readily available
inspection tag attached to the accessible grounding electrode reinforcing
bar.
d. The grounding electrode
conductor connection to the concrete encased electrode shall be inspected by
the electrical inspector for the enforcing agency .
E3609.7.1.
Corrugated stainless steel tubing (CSST). Corrugated stainless steel tubing gas
piping systems shall be bonded to the electrical service grounding electrode
system or where provided, lightening protection electrode system . The bonding
jumper shall connect to a metallic pipe, pipe fitting, or CSST fitting between
the point of delivery and the CSST utilizing a device listed for the
application . The bonding jumper shall be not smaller than 6 AWG copper wire or
equivalent , not longer than 75 feet and accessible. Gas piping systems that are
bonded in accordance with this section shall be considered effectively bonded
regardless of the amount of CSST in the system . Any additional grounding
electrodes used shall be bonded to the electrical service grounding electrode
system , or where provided, the lighting protection grounding electrode system .
Exception: CSST piping systems tested and
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.