Mich. Admin. Code R. 408.30537a - Wiring methods
Rule 537a.
Section E3803.6 and tables E3801.4, and E3802.1 are amended to read as follows:
TABLE E3802.1
GENERAL
|
AC MC |
EMT IMC RMC |
ENT |
FMC LFC |
NM UF |
PVC |
SE |
SRa |
Where run parallel with the framing |
A |
- |
A |
A |
A |
- |
A |
- |
Bored holes in framing members for wiring shall
be located not less than 1 1/4 inches from the edge of the framing |
Ak |
- |
Ak |
Ak |
Ak |
- |
Ak |
- |
Where installed in grooves, to be covered by
wallboard, siding, paneling, carpeting, or similar finish, wiring methods shall
be protected by 0.0625-inch-thick steel plate, sleeve, or |
A |
- |
A |
A |
A |
- |
A |
A |
Securely fastened bushings or grommets shall be provided to protect wiring run through openings in metal framing members. |
- |
- |
Aj |
- |
Aj |
- |
Aj |
- |
The maximum number of 90-degree bends shall not exceed 4 between junction boxes. |
- |
A |
A |
A |
- |
A |
- |
- |
Bushings shall be provided where entering a
box, fitting, or enclosure unless the box or fitting is designed to afford
|
A |
A |
A |
A |
- |
A |
- |
A |
Ends of raceways shall be reamed to remove rough edges. |
- |
A |
A |
A |
- |
A |
- |
A |
Maximum allowable on center support spacing for the wiring method in feet. |
4.5b,c |
10l |
3b |
4.5b |
4.5i |
3d, l |
2.5e |
- |
Maximum support distance in inches from box or other terminations. |
12b, f |
36 |
36 |
12b, g |
12h, i |
36 |
12 |
- |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 degree = 0.0175 rad.
Such raceways shall
Notes