Mich. Admin. Code R. 408.30537a - [Rescinded effective 8/29/2025] Wiring methods
Rule 537a.
Section E3803.6 and tables E3801.4, and E3802.1 are amended to read as follows:
TABLE E3802.1
GENERAL INSTALLATION AND SUPPORT REQUIREMENTS FOR WIRING METHODSa,b, c, d, e, f, g, h, i, j, k
|
INSTALLATION REQUIREMENTS (Requirement applicable only to wiring methods marked "A") |
AC MC |
EMT IMC RMC |
ENT |
FMC LFC |
NM UF |
PVC |
SE |
SRa |
|
Where run parallel with the framing member or furring strip, the wiring shall be not less than 1 1/4 inches from the edge of a furring strip or a framing member such as a joist, rafter, or stud or shall be physically protected. |
A |
- |
A |
A |
A |
- |
A |
- |
|
Bored holes in framing members for wiring shall be located not less than 1 1/4 inches from the edge of the framing member or shall be protected with a minimum 0.0625-inch steel plate or sleeve, a listed steel plate, or other physical protection. |
Ak |
- |
Ak |
Ak |
Ak |
- |
Ak |
- |
|
Where installed in grooves, to be covered by wallboard, siding, paneling, carpeting, or similar finish, wiring methods shall be protected by 0.0625-inch-thick steel plate, sleeve, or equivalent, a listed steel plate or by not less than 1 1/4-inch free space for the full length of the groove in which the cable or raceway is installed. |
A |
- |
A |
A |
A |
- |
A |
A |
|
Securely fastened bushings or grommets shall be provided to protect wiring run through openings in metal framing members. |
- |
- |
Aj |
- |
Aj |
- |
Aj |
- |
|
The maximum number of 90-degree bends shall not exceed 4 between junction boxes. |
- |
A |
A |
A |
- |
A |
- |
- |
|
Bushings shall be provided where entering a box, fitting, or enclosure unless the box or fitting is designed to afford equivalent protection. |
A |
A |
A |
A |
- |
A |
- |
A |
|
Ends of raceways shall be reamed to remove rough edges. |
- |
A |
A |
A |
- |
A |
- |
A |
|
Maximum allowable on center support spacing for the wiring method in feet. |
4.5b,c |
10l |
3b |
4.5b |
4.5i |
3d, l |
2.5e |
- |
|
Maximum support distance in inches from box or other terminations. |
12b, f |
36 |
36 |
12b, g |
12h, i |
36 |
12 |
- |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 degree = 0.0175 rad.
Such raceways shall terminate in an outlet box, junction box, device box, cabinet, or other termination at each end of the raceway.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
Rule 537a.
Section E3803.6 and tables E3801.4, and E3802.1 are amended to read as follows:
TABLE E3802.1
GENERAL
| | AC MC | EMT IMC RMC | ENT | FMC LFC | NM UF | PVC | SE | SRa |
| Where run parallel with the framing | A | - | A | A | A | - | A | - |
| Bored holes in framing members for wiring shall be located not less than 1 1/4 inches from the edge of the framing | Ak | - | Ak | Ak | Ak | - | Ak | - |
| Where installed in grooves, to be covered by wallboard, siding, paneling, carpeting, or similar finish, wiring methods shall be protected by 0.0625-inch-thick steel plate, sleeve, or | A | - | A | A | A | - | A | A |
| Securely fastened bushings or grommets shall be provided to protect wiring run through openings in metal framing members. | - | - | Aj | - | Aj | - | Aj | - |
| The maximum number of 90-degree bends shall not exceed 4 between junction boxes. | - | A | A | A | - | A | - | - |
| Bushings shall be provided where entering a box, fitting, or enclosure unless the box or fitting is designed to afford | A | A | A | A | - | A | - | A |
| Ends of raceways shall be reamed to remove rough edges. | - | A | A | A | - | A | - | A |
| Maximum allowable on center support spacing for the wiring method in feet. | 4.5b,c | 10l | 3b | 4.5b | 4.5i | 3d, l | 2.5e | - |
| Maximum support distance in inches from box or other terminations. | 12b, f | 36 | 36 | 12b, g | 12h, i | 36 | 12 | - |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 degree = 0.0175 rad.
Such raceways shall