Mich. Admin. Code R. 408.30539a - [Effective until 8/29/2025] Automatic fire sprinkler systems
Rule 539a. Sections R313.1, P2902.5.4 and P2904.1 of the code are amended to read as follows:
R313.1. Design and installation. Where
installed, automatic residential fire sprinkler systems shall conform to the
design and installation requirements of the national fire protection
association (NFPA) standard 13D or P2904.1.
P2902.5.4. Connections to automatic fire
sprinkler systems. The potable water supply to automatic fire sprinkler systems
shall be protected against backflow by a double check-valve assembly or a
reduced pressure principle backflow preventer.
Exception: Isolation of the water distribution system is not required for deluge, preaction, or dry pipe system.
P2904.1. General. Where installed,
residential fire sprinkler systems, or portions thereof, shall be in accordance
with NFPA 13D.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
Rule 539a. Sections R313.1, P2902.5.4 and P2904.1 of the
R313.1. Design and installation . Where installed, automatic residential fire sprinkler systems shall conform to the design and installation requirements of the national fire protection association (NFPA ) standard 13D or P2904.1.
P2902.5.4. Connections to automatic fire sprinkler systems. The potable water supply to automatic fire sprinkler systems shall be protected against backflow by a double check-valve assembly or a reduced pressure principle backflow preventer.
Exception:
P2904.1. General. Where installed, residential fire sprinkler systems, or portions thereof, shall be in accordance with NFPA 13D.