Rule 547d.
Sections N1102.2.6, N1102.2.12, N1102.3.3, N1102.3.6,
N1102.4, N1102.4.1.1, N1102.4.1.2, N1102.4.2, N1102.4.3, N1102.4.4, tables
N1102.1.1, N1102.1.3, and N1102.4.1.1 of the code are amended to read as
follows:
N1102.2.6 (R402.2.6).
Steel-frame ceilings, walls, and floors. Steel-frame ceilings, walls, and
floors shall meet the insulation requirements of table N1102.2.6 or shall meet
the U-factor requirements in table N1102.1.3. The calculation of the U-factor
for a steel-frame envelope assembly shall use a series-parallel path
calculation method.
N1102.2.12
Thermally isolated sunroom insulation. The minimum ceiling insulation R-values
shall be R-24 in zones 5 to 7. The minimum wall R-value shall be R-13 in all
zones. New wall or walls separating a sunroom from conditioned space shall meet
the building thermal envelope requirements.
N1102.3.3 (R402.3.3). Glazed fenestration
exemption. Up to 15 square feet (1.4m
2) of glazed
fenestration per dwelling unit may be exempt from U-factor requirements in
section N1102.1.1.
This exemption shall not apply to the U-factor
alternative approach in section N1102.1.1 and the total UA alternative in
section N1102.1.4.
N1102.3.6 (R402.3.6). Replacement
fenestration. Where some or all of an existing fenestration unit is replaced
with a new fenestration product, including sash and glazing, the replacement
fenestration unit shall meet the applicable requirements for U-factor in table
N1102.1.3. Where some or all of an existing fenestration unit is replaced with
a new fenestration product, including sash and glazing, the replacement
fenestration unit shall meet the applicable requirements for U-factor in table
N1102.1.1.
N1102.4 (R402.4). Air
leakage. The
building thermal envelope shall be constructed to limit air
leakage in accordance with the requirements of sections N1102.4.1 through
N1102.4.4.
N1102.4.1 (R402.4.1).
Building
thermal envelope. The
building thermal envelope shall comply with sections
N1102.4.1.1 and N1102.4.1.2.
N1102.4.1.1
(R402.4.1.1). Installation (mandatory). The components of the building thermal
envelope as listed in table N1102.4.1.1 shall be installed in accordance with
the manufacturers instructions and the criteria listed in table N1102.4.1.1, as
applicable to the method of construction. The sealing methods between
dissimilar materials shall allow for differential expansion and
contraction.
N1102.4.1.2
(R402.4.1.2). Testing (prescriptive). The
building or dwelling unit shall be
tested and verified as having an air leakage rate of not exceeding 4 air
changes per hour. Testing shall be conducted with a blower door at a
pressure
of 0.2" w.g. (50 pascals). Where required by the
code official, testing shall
be conducted by a
certified independent
third party. Certification programs
shall be
approved by the state construction
code commission. A
written report
of the results of the
test shall be
signed by the
party conducting the
test and
provided to the
code official. Testing shall be performed at any time after
creation of all penetrations of the
building thermal envelope.
During testing all of the following apply:
1. Exterior windows and doors, fireplace, and
stove doors shall be closed, but not sealed, beyond the intended weather
stripping or other infiltration control measures.
2. Dampers including exhaust, intake, makeup
air, backdraft, and flue dampers shall be closed, but not sealed beyond
intended infiltration control measures.
3. Interior doors, if installed at the time
of the test, shall be open.
4.
Exterior doors for continuous ventilation systems and heat recovery ventilators
shall be closed and sealed.
5.
Heating and cooling systems, if installed at the time of the test, shall be
turned off.
6. Supply and return
registers, if installed at the time of the test, shall be fully open.
N1102.4.2 (R402.4.2).
Fireplaces (mandatory). New wood-burning masonry fireplaces shall have
tight-fitting flue dampers and outdoor combustion air.
N1102.4.3 (R402.4.3). Fenestration air
leakage (mandatory). Windows, skylights, and sliding glass doors shall have an
air infiltration rate of no more than 0.3 cfm per square foot (1.5
L/s/m
2), and swinging doors no more than 0.5 cfm per
square foot (2.6 L/s/m
2), when tested according to
NFRC 400 or AAMA/WDMA/
CSA 101/I.S.2/A440 by an accredited, independent
laboratory and
listed and
labeled by the manufacturer.
Exception: Site-built windows, skylights, and
doors.
N1102.4.4
(R402.4.4). Recessed lighting (mandatory). Recessed luminaires installed in the
building thermal envelope shall be sealed to limit air leakage between
conditioned and unconditioned spaces. All recessed luminaires shall be IC-rated
and
labeled as having an air leakage rate not more than 2.0 cfm (0.944 L/s)
when tested in accordance with ASTM E 283 at a 1.57 psf (75 Pa)
pressure
differential. All recessed luminaires shall be sealed with a gasket or caulk
between the housing and the interior wall or ceiling covering.
TABLE N1102.1.1 (R402.1.1)
INSULATION AND FENESTRATION REQUIREMENTS BY
COMPONENTa
Climate Zone
|
Fenestration
U-Factorb
|
Skylightb
U-Factor
|
Ceiling R-Value
|
Wood Frame Wall RValue
|
Mass Wall
R-Valueg
|
Floor R-Value
|
Basementc
Wall R-Value
|
Slabd
R-Value & Depth
|
Crawl
Spacec
Wall R-Value
|
5A
|
0.32
|
0.55
|
38
|
20 or 13 + 5f
|
13/17
|
30e
|
10/13
|
10, 2 ft
|
15/19
|
6A
|
0.32
|
0.55
|
49
|
20 or 13 + 5f
|
15/20
|
30e
|
15/19
|
10, 4 ft
|
15/19
|
7
|
0.32
|
0.55
|
49
|
20 or 13 + 5f
|
19/21
|
38e
|
15/19
|
10, 4 ft
|
15/19
|
a. R-values
are minimums. U-factors are maximums. When insulation is installed in a cavity
which is less than the label or design thickness of the insulation, the
installed R-value of the insulation shall not be less than the R-values
specified in the table.
b. The
fenestration U-factor column excludes skylights.
c. "15/19" means R-15 continuous insulation
on the interior or exterior of the home or R-19 cavity insulation at the
interior of the basement wall. "15/19" may be met with R-13 cavity insulation
on the interior of the basement wall plus R-5 continuous insulation on the
interior or exterior of the home. "10/13" means R-10 continuous insulation on
the interior or exterior of the home or R-13 cavity insulation at the interior
of the basement wall.
d. R-5 shall
be added to the required slab edge R-values for heated slabs.
e. Or insulation sufficient to fill the
framing cavity, R-19 minimum.
f.
First value is cavity insulation, second is continuous insulation or insulated
siding, so "13 + 5" means R-13 cavity insulation plus R-5 continuous insulation
or insulated siding. If structural sheathing covers 40% or less of the
exterior, continuous insulation R-value may be reduced by no more than R-3 in
the locations where structural sheathing is used to maintain a consistent total
sheathing thickness.
g. The
second
R-value applies when more than 1/2 the insulation is on the interior of the
mass wall.
TABLE N1102.1.3 (R402.1.3)
EQUIVALENT U-FACTORSa
Climate Zone
|
Fenestration U-Factor
|
Skylight U-Factor
|
Ceiling U-Factor
|
Frame Wall U-Factor
|
Mass Wall
U-Factorb
|
Floor U-Factor
|
Basement
Wall
U-Factor
|
Crawl
Space
Wall
U-Factor
|
5A
|
0.32
|
0.55
|
0.030
|
0.057
|
0.082
|
0.033
|
0.059
|
0.055
|
6A
|
0.32
|
0.55
|
0.026
|
0.057
|
0.060
|
0.033
|
0.050
|
0.055
|
7
|
0.32
|
0.55
|
0.026
|
0.057
|
0.057
|
0.028
|
0.050
|
0.055
|
a. Nonfenestration U-factors shall be
obtained from measurement, calculation, or an approved source.
b. When more than half the insulation is on
the interior, the mass wall U-factors shall be a maximum of 0.065 in zone 5 and
marine 4, and 0.057 in zones 6 and 7.
TABLE N1102.4.1.1 (R402.4.1.1)
AIR BARRIER AND INSULATION INSTALLATION
COMPONENT
|
CRITERIAa
|
Air barrier and thermal barrier
|
A continuous air barrier shall be installed in
the building envelope. Exterior thermal envelope contains a continuous air
barrier. Breaks or joints in the air barrier shall be sealed. Air-permeable
insulation shall not be used as a sealing material.
|
Ceiling/attic
|
The air barrier in any dropped ceiling/soffit
shall be aligned with the insulation and any gaps in the air barrier
sealed.
Access openings, drop down stair, or knee wall
doors to unconditioned attic spaces shall be sealed.
|
Walls
|
Corners and headers shall be insulated and the
junction of the foundation and sill plate shall be sealed.
The junction of the top plate and top of
exterior walls shall be sealed. Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and continuous alignment with
the air barrier. Knee walls shall be sealed.
|
Windows, skylights, and doors
|
The space between window/door jambs and
framing, and skylights and framing shall be sealed.
|
Rim joists
|
Rim joists shall be insulated and include the
air barrier.
|
Floors
(including above-garage and cantilevered
floors)
|
Insulation shall be installed to maintain
permanent contact with underside of subfloor decking.
The air barrier shall be installed at any
exposed edge of insulation.
|
Crawl space walls
|
Where provided in lieu of floor insulation,
insulation shall be permanently attached to the crawlspace walls.
Exposed earth in unvented crawl spaces shall be
covered with a class I vapor retarder with overlapping joints taped.
|
Shafts, penetrations
|
Duct shafts, utility penetrations, and flue
shafts opening to exterior or unconditioned space shall be sealed.
|
Narrow cavities
|
Batts in narrow cavities shall be cut to fit,
or narrow cavities shall be filled by insulation that on installation readily
conforms to the available cavity space.
|
Garage separation
|
Air sealing shall be provided between the
garage and conditioned spaces.
|
Recessed lighting
|
Recessed light fixtures installed in the
building thermal envelope shall be air tight, IC rated, and sealed to the
drywall.
|
Plumbing and wiring
|
Batt insulation shall be cut neatly to fit
around wiring and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall extend behind piping and
wiring.
|
Shower/tub on exterior wall
|
Exterior walls adjacent to showers and tubs
shall be insulated and the air barrier installed separating them from the
showers and tubs.
|
Electrical/phone box on exterior walls
|
The air barrier shall be installed behind
electrical or communication boxes or air-sealed boxes shall be
installed.
|
HVAC register boots
|
HVAC register boots that penetrate the building
thermal envelope shall be sealed to the subfloor or drywall.
|
Fireplace
|
An air barrier shall be installed on fireplace
walls.
|
a. In addition, inspection of log walls shall
be in accordance with the provisions of ICC-400.